Hawsepiper
Engineer
By the book
The ship
By the problem
Drills
Simulators
Find anything
Fact check
Blog
ETO
Find anything
Every lesson, worksheet, simulator and tool
Type a word: “flash cards”, “PLC”, “megger”, “tour”, or an ETO entry number like 4.12.
Lessons
(135)
Lesson
AC and Three-Phase: What the Meter Is Telling You
DG2 at 59.3 Hz is an engine running slow. RMS and peak, true-RMS against average-responding on a UPS feed and a drive output, the voltmeter selector, and wye and delta windings.
Lesson
Arrangement Drawings
The engine room’s electric equipment arrangement: read the sheet’s edges, find JB-12, GSP-1 and IO-2 by deck, frame and side, then trace three dead alarms to the one box they share and walk there.
Lesson
Battery Load Test and Replacement
Hawsepiper’s engine room 24 V bank on its real load: CH2 off, logged against August, done at 54 minutes. Then the one low cell, how each bank is tested, and the change, like for like.
Lesson
Before You Open the Box
MAC1 trips ten seconds after every start. Five minutes before the screwdriver: the drawing, the alarm history and the log, what changed last, and only then the box.
Lesson
Board-Level Repair: When There Is No Spare Board
FOP2’s power and output board, no spare and the exchange three weeks off: whose board it is, look then measure, the right parts and polarity, the iron and the job in order, and when to stop.
Lesson
Bus Tie and Rack-Out Breakers
What a bus tie is for, every part inside an air circuit breaker, how it closes and trips, racking it out safely, and finding out why it won't close.
Lesson
Cables, Glands, Penetrations and the Cable Number
Read a marine cable inside out and a tag against the cable list, find what people did to a tray, judge five glands on a wet deck box, and find the hole a contractor left in an A-60 transit.
Lesson
Calibrate or Replace a Transmitter
DG2’s LO pressure transmitter has drifted: isolate, vent, take the as-found, chase zero and span until both hold, check the middle. Then pick a replacement that matches all five things.
Lesson
Control Power: 110 V and 24 V DC
The board’s own 110 V DC supply and the automation’s 24 V: chargers and batteries through a blackout, reading the charger and battery ammeters, a charger that quit two days before anyone noticed, a blown control fuse, and six calls.
Lesson
DC Grounds: Floating or Chassis-Grounded
Floating 110 V and 24 V with + and − lamps, and the EDG engine’s 24 V with its negative on the block: pull breakers, split at junction boxes, meter across the device, hunt a short.
Lesson
Deck Cranes: Hoist, Slew, Luff, Brakes, Limits
Deck crane CR1: whose parts are whose, a crane that cuts out slewed to port, the hoist chain, limits first from the diagnostic page, three valve-coil faults, and six calls.
Lesson
ECDIS Updates: Both Machines, Every Time
ECDIS 2 two weeks behind ECDIS 1: the update path traced, weeks 44 and 45 loaded by the procedure, a missing permit found, then new software one machine at a time.
Lesson
Engine Safety: Slowdown and Shutdown
The main engine’s own safety system: its sensors, the slowdown and shutdown lists, the bridge cancel and what it can’t cancel, a 02:10 stop traced to one switch, the test schedule, five calls.
Lesson
Engines You’ll See: Telling the Families Apart
Hawsepiper’s three engine families, crosshead against trunk, speed class, reading a type designation, the free end and cylinder numbers, the seven day-one steps, and where each family keeps its trouble.
Lesson
Exchange and PA Faults: Find the Dead Bit
Hawsepiper’s PA and telephone exchange, the next month: a dead zone relay, a wet forecastle horn found by splitting the line, a dead line-card port, and BDB-8 tripped behind a flat battery.
Lesson
Fans and Blowers
No. 2 ER supply fan, the boiler FD fan and an AHU: push an axial fan into stall, two centrifugal wheels with opposite amps, a reversed fan found by hand, a belt, a sticking fire damper, six readings.
Lesson
Fasteners, Gaskets and Packing: A Shop Drill
Read bolt heads and pick a replacement; identify two threads; find a torque with its lubricant and unit; tighten LT1's feet across in three passes and a check round; cut a gasket; pack a fire pump gland to a drip; free a seized nut; five calls.
Lesson
Filters and Strainers
The duplex strainer on the fuel supply pump suction: ΔP against dirt, flow, cold fuel and a tear; change over without losing suction; prove it dead with the QCV as third valve; five types; seven readings.
Lesson
Five Ways to Talk: Internal Comms
Hawsepiper’s telephone exchange, PA, talkback, sound-powered phones and general alarm: how each works, what feeds it, what still talks in a blackout, and the two tests nobody else does.
Lesson
Fuel Injection: From Pump to Flame
On Hawsepiper’s camshaft main engine: build a jerk pump part by part, bar it round at three rack settings, pop test four fuel valves, read Pcomp, Pmax and exhaust as a pair, find a creeping rack linkage, compare an electronic engine, then find why No. 4 runs cold.
Lesson
Galley and Laundry: The Calls the Crew Sees
Range 1’s hotplate that only does Low, found in the selector switch; Range 2’s infinite switches; walk the cycle on a dishwasher, a combi oven and a dryer; a laundry GFCI that has found a washer.
Lesson
GMDSS: The Station, the Radios, the Batteries
Hawsepiper’s radio station: every set and what feeds it, the 24 V through a blackout and a dead ship, the three kinds of test, a failed MF/HF test call traced to the aerial, a charger that stopped charging.
Lesson
Ground Hunting
What a ground is on an insulated ship and why one trips nothing; reading the ground lamps and the insulation monitor; splitting the 220 V board once you have the go-ahead; then the megger or the multimeter, and which one for what.
Lesson
Ground Lamps and the Ground Hunt
Read the three ground lamps and the insulation monitor, name the island a ground is on, half-split the board down to a wet deck light, and find a ground on a feeder that can’t be dropped with the leakage clamp.
Lesson
Ground, Short or Open: Which Do You Have?
Let the symptom pick the test: ohms between conductors for a short, the megger to hull for a motor ground (multimeter for lighting), continuity end to end for an open. Then the readings that fool people.
Lesson
Gyro, Autopilot and Steering: One Loop
Follow Hawsepiper’s steering round one loop: heading in, decision, command out, rudder back. Auto, FU, NFU and the flat; four complaints found by part; a slipped transmitter reset; the gyro brought back.
Lesson
Hand Tools and Measurement: A Hands-On Drill
Pick wrench, hammer and puller from the tool board; read a micrometer and a vernier caliper; set a valve lash with feelers; find a hub’s run-out with a dial indicator; work a torque figure for oil, an adapter and ft·lbf and tighten across the circle; count the board before box-up.
Lesson
Heat Exchangers
No. 1 central cooler: four temperatures, two ΔPs and the five approach patterns; which way a LO cooler leaks running and stopped; on and off line in order; a plate pack closed to its dimension; seven readings.
Lesson
How Automation Breaks
Is the reading wrong, or the plant? The six checks walked on DG2’s LO pressure over five days, an alarm that won’t clear set beside its limit, three nuisance trends, the first stop for every other symptom, and a dark cabinet traced back up its feed.
Lesson
How Bridge Gear Breaks: Symptom to First Check
The Part 6 round-up: eight Hawsepiper cases on the book’s tree, then a dead echo sounder, four nights of alarms that are one feed each, a weak radio, and a radar that loses heading in a seaway.
Lesson
How Distribution Breaks
Part 3 in one sitting: eight distribution symptoms sorted to their first check, then three walked on M/V Hawsepiper: a trip with nothing changed, a trip every start, and lights that dim and stay dim.
Lesson
How Hotel Systems Break
Part 7 round-up on Hawsepiper: sort eight calls into water, heat, vibration and neglect; then a UPS alarm, a fire panel fault, a tripping galley GFCI and a machine you have never seen.
Lesson
How Motors Break
Part 4 in one sitting: eight places a motor breaks, ten symptoms sorted to their first check, then three walked on Hawsepiper: hums and won’t turn, trips the breaker on start, runs, stops, runs.
Lesson
How to Use This Site
A short orientation: the three billets, the four learning stages, the ways in (by the book, by the ship, by the problem), what a lesson, plant tour, worksheet, simulator and Fault Bench each are, and where to start.
Lesson
HVAC and Provision Plant Repairs
Four repairs on Hawsepiper’s cooling: a part-winding compressor’s two contactors, a pressure switch isolated at its service valves and set by the gauge, a fan motor matched and turned the right way, a controller rewired and typed.
Lesson
ICCP, Shaft Grounding and Marine Growth Prevention
The hull’s own electrical system: hold the hull in its band, read four weeks of ICCP log, find a worn shaft brush from its millivolts, and change an MGPS anode that can’t hold its current.
Lesson
Isolate a Loop Fault, Swap a Detector or Call Point
Loop B’s drilled cable lost as B-008 to B-011: lift the section at ISO-2 and ISO-3, meter it, half-split at the bases to the drill hole, repair and confirm; then swap a dusty head and a cracked call point.
Lesson
Keeping the Drawings True
The sludge pump won’t start and its sheet says it should: find the low-level cut-out nobody drew, red-line it, get it into the master set, then red-line the BWTS and the bigger AC breaker on E-101.
Lesson
kW, kVAR, kVA and Power Factor
The meter-in-hand theory under the generator panel: two plates on DG1, SWP1’s triangle from a clamp and a voltmeter, a motor running light, a set at its ammeter limit with kW to spare, two sets not sharing kVAR.
Lesson
Lighting: Ballasts, LED Drivers and Wet Fittings
Inside a fluorescent, an LED and an incandescent fitting and which part fails; four purifier room fluorescents; two dead LED floods on the bench; 120 LED drivers that look like a ground; four wet deck floods.
Lesson
Load the Meter
Eighty volts on a deck lighting circuit you’ve just isolated: load the meter and watch the ghost collapse, then find the one that doesn’t; prove the meter live, dead, live; and four calls.
Lesson
Lubricants and Greases: The Right One, the Right Amount
Match the lube oil store to seven fill points, grades and BN against the fuel, three unlabelled cans, grease by thickener, grease LT1’s motor bearing by grams with the relief plug out, read what comes out, and put right a steering gear topped up with engine oil.
Lesson
Make a Bronze Bushing on the Lathe
The book’s worked example on M/V Hawsepiper: what to make aboard, the lathe made safe, the fits worked out, the tool on center and the speed, the bushing made in order, the micrometer read warm and cold, then fitted and five workshop calls.
Lesson
Make Up a Cable End and Gland
A deck box that filled with water through its gland: find the six faults in the old end, then make up the new one. Strip to the gland, braid into the cone, tighten and pull, ferrule, number, slack.
Lesson
Megger a Motor and Dry It Out
Test the emergency fire pump motor alone at 500 V for one minute, winding to frame and winding to winding, dry it out without cooking it, and read the curve: wet, ending or faulted.
Lesson
Motor Controllers
What an across-the-line starter does, start and stop with the seal-in, setting and resetting the overload, reversing with two interlocked contactors on the engine room crane, and the top faults.
Lesson
Ohm’s Law: The Missing Number
A purifier heater fuse with no rating on the drawing: meter the element, work out the current and pick the fuse. Three quick ones, then volts across a lug under load.
Lesson
One Fault at a Time, and the Second One Water Makes
No. 2 hold bilge pump won’t start: find one corroded terminal in the wet float box, fix it, test again from the load, and find the second it was hiding. Then three changes with no record, and an intermittent.
Lesson
Packaged Controllers
The boiler, purifier, compressor and AC cabinets are the same inside: sort what is electrical, mechanical and the maker’s; read a purifier’s alarm history and manual on three days; prove the common alarm reaches the ship after a cabinet change; five calls.
Lesson
Phase Rotation: Prove It, Swap It at the Motor
No. 1 ER supply fan bumped backward after its cable was renewed: crossed cores found, two swapped at the motor. Then a reversed LT pump that sounds fine, and SWP1’s six leads by the drawing.
Lesson
PID: Controller or Valve?
The main engine jacket water swings five degrees either side of 85 °C the day after a positioner change. Read the shape of the swing, stroke the valve, and say whether it is the controller or the valve before anyone turns a knob.
Lesson
Pipe Work: Prove It Dead, Clamp It, Renew It
A pinhole in M/V Hawsepiper’s ballast discharge: prove the line dead, pick the repair the book allows on each service and who signs it off, fit a clamp on sound metal, thread a nipple to the right length, break and make up a flange in a star, test it and three calls.
Lesson
Piping, Flanges and Gaskets
Name five lines by magnet and eye; measure a bolt circle and find why the spare won't fit; pick gaskets for six joints; bolt a Cu-Ni flange in the star; a steam line growing between anchors; trace a leak; five pipe calls.
Lesson
Plant Tour: Ballast and Ballast Water Treatment
Walk Hawsepiper’s ballast plant stop by stop on one drawing of the ship, from the sea chests through the ballast pumps, the filter and UV treatment system and the remote valves to the tanks, soundings and vents, the stripping eductor and the ballast console in the ship’s office: what to look at, what normal reads, a call at each stop; then nine sets of readings.
Lesson
Plant Tour: Bilge, Oily Water Separator, Sludge and Incinerator
Walk Hawsepiper’s bilge and sludge plant stop by stop on one drawing of the engine room, from the bilge wells through the holding tank, the separator and its 15 ppm monitor to the sludge tank, sludge pump, incinerator and Oil Record Book: what to look at, what normal reads, a call at each stop; then six sets of readings.
Lesson
Plant Tour: Compressed Air
Walk Hawsepiper’s compressed air plant stop by stop on one drawing of the engine room, from MAC1 and MAC2 to the air start valves and the control air header: what to look at, what normal reads, a call at each stop; then eight sets of readings.
Lesson
Plant Tour: Fire Protection
Walk Hawsepiper’s fire protection stop by stop on one side view of the aft end, from the fire pumps and the emergency fire pump to the fire main, CO₂, water mist, detection and the shutdowns: what to look at, what normal reads, a call at each stop; then eight sets of readings.
Lesson
Plant Tour: Hydraulics
Walk the hydraulic pattern stop by stop on deck crane CR1 cut open, with No. 2 hatch cover, its power unit and the engine room’s remote valve power unit beside it: tank, pump, filters, cooler, accumulators, relief, valves, actuators, hoses and the other users; then six sets of readings.
Lesson
Plant Tour: Propulsion Beyond the Engine
Walk Hawsepiper’s shaft line stop by stop on one side view of the aft end, from the thrust bearing and turning gear to the stern tube and the fixed-pitch propeller, with insets for a geared ship, a CPP ship and the bow thruster; then seven sets of readings.
Lesson
Plant Tour: Refrigeration and HVAC
Walk Hawsepiper’s provision plant and air conditioning stop by stop on one drawing of the aft end, from the compressor round the cycle to the meat, veg and dairy rooms, then the AHU and the engine room supply fans: what to look at, what normal reads, a call at each stop; then six sets of readings.
Lesson
Plant Tour: Seawater and Central Cooling
Walk Hawsepiper’s cooling plant stop by stop on one drawing of the engine room, from the sea chests to the water treatment: follow the sea water, then the heat; a call at each stop; then seven sets of readings.
Lesson
Plant Tour: Sewage and Gray Water
Walk Hawsepiper’s vacuum toilets and sewage plant stop by stop on one drawing of the aft end, from the toilets and vacuum piping to the collection tank, the treatment plant with its blower and float-run discharge pump, the chlorinator, the overboard valve and the gray water: what to look at, what normal reads, a call at each stop; then seven sets of readings.
Lesson
Plant Tour: Steering Gear
Walk Hawsepiper’s steering gear stop by stop on one plan of the steering flat, with the bridge stand and the two boards beside it: control systems, power units and feeders, valve block, rams, stock and feedback, local control; then six sets of readings.
Lesson
Plant Tour: The Electrical Plant
Walk Hawsepiper’s electrical plant stop by stop on one drawing of the engine room and the accommodation above it, from the emergency generator to the shore connection: what to look at, what normal reads, a call at each stop; then six sets of readings.
Lesson
Plant Tour: The Freshwater Plant
Walk Hawsepiper’s freshwater plant stop by stop on one drawing of the engine room and the accommodation above it, from the sea chest and the evaporator to the hydrophore and the hot water loop: what to look at, what normal reads, a call at each stop; then nine sets of readings.
Lesson
Plant Tour: The Fuel Plant
Walk Hawsepiper’s fuel plant stop by stop on one drawing of the engine room, from the bunker manifold to the main engine: what to look at, what normal reads, a call at each stop; then five sets of readings.
Lesson
Plant Tour: The Lube Oil Plant
Walk Hawsepiper’s lube oil plant stop by stop on one drawing of the engine room, from the deck filling station to the waste oil tank: what to look at, what normal reads, a call at each stop; then seven sets of readings.
Lesson
Plant Tour: The Main Engine as a Loop
Walk Hawsepiper’s slow-speed two-stroke main engine as one loop, stop by stop on one drawing: air in, compression, injection, combustion and power, exhaust, the turbocharger and exhaust gas boiler, power out and the three supports; then eight sets of readings.
Lesson
Plant Tour: The Steam Plant
Walk Hawsepiper’s steam plant stop by stop on one drawing of the engine room, from the auxiliary boiler and the exhaust gas boiler to the hotwell and the blowdown: what to look at, what normal reads, a call at each stop; then seven sets of readings.
Lesson
Preferential Trip and Load Shedding
Sort the feeders into stages and the never-shed list, watch a set trip and the board shed load to save the last set, the blackout without it, capacity before putting the load back, and why a set over its share can shed the galley.
Lesson
Protective Relays: Read the Flag
What each of the five generator relays watches; a reverse power trip after a slow close; overcurrent that rides through a motor start; the AVR’s relays against the governor’s; differential and its zone; a multifunction relay’s event log; and six trips to sort.
Lesson
Pull a Motor, Fit New Bearings, Line It Up
No. 1 LT pump’s drive-end bearing has gone. Mark it before it comes off, bench-test it, heat new bearings on, run it uncoupled, then align it: soft foot, angular, offset, torque, re-check.
Lesson
Radar Reset, Magnetron Change, Unit Swap
Radar S again: a frozen picture reset from the breaker, the 7,990-hour magnetron changed up the mast and tuned, and a new processor that needs the ship’s settings.
Lesson
Radio Battery: The Load Test and the Change
Hawsepiper’s GMDSS reserve on load with the bridge: open BDB-10, log an hour against last time, confirm it charges. Then a bank that falls faster, a weak block, and the change like for like.
Lesson
Reading a Wiring Diagram and a Ladder
The No. 1 LT pump starter drawn as a ladder and as a wiring diagram. Find each part on both, trace a rung, follow wire and terminal numbers, and go from the ladder to the right two screws.
Lesson
Reading the Switchboard Like a Story
Five meters on each generator panel and the stories they tell: equal kW with unequal amps, unequal kW at the right frequency, a plant near its limit, poor power factor, low volts on every set.
Lesson
Reefer Receptacles and the Monitoring System
The ship’s side of the reefers: the feeder to forty receptacles, the load on loading day, plugging in and out without burning pins, a rain ground found receptacle by receptacle, and the office screen read right.
Lesson
Refrigeration and HVAC: A Motor and a Chain of Safeties
The provision plant’s compressor rung opened one safety at a time; the wiring or the card; an HP trip read before the reset, an LP short-cycle settled at the sight glass, an iced coil traced to its timer.
Lesson
Repair a 440 V Motor Cable: The Three-Tape Method
No. 1 LT pump’s lead cracked at the gland: prove it dead at the motor, find the core, clean it, rubber twice and vinyl over, megger it, fix the gland. Then cooked leads in FOP2’s box.
Lesson
Repair a Fixture; GFCI Circuits
The accommodation ladder light: prove it dead at the fitting (it has two feeds), find how the water got in, ohm it to hull before it goes back on. Then how a GFCI decides, and the one that won’t stay in.
Lesson
Replace a Breaker, Fuse, Relay or Terminal
The five things on a breaker label, a galley breaker swapped with the feeder above locked out; three fuses matched by type, rating and speed; MAC1’s trip relay matched by coil and contacts; a hot terminal.
Lesson
Replacing Motor Bearings
The No. 1 LT pump motor’s drive-end bearing has gone. Mark it before it comes off, pull the old bearings with a puller, match 6311-C3 and 6211-C3, heat the new ones on to about 110 °C, run it uncoupled, then line it up.
Lesson
Rigging and Lifting: A Motor Out of the Engine Room
LT1’s motor goes ashore from M/V Hawsepiper: the gear inspected and three items tagged out, the weight from the plate, the chain block on the padeye, sling angles worked out, the load handed to the 5 t engine room crane, signals, the landing, and five calls.
Lesson
RTDs and Thermocouples: Ohms and Millivolts
DG2’s temperature points sorted into Pt100s and thermocouples; GE224 ohmed against the table at both ends, then found linked as two-wire; No. 4 exhaust low and slow; a new thermocouple fitted.
Lesson
Series and Parallel: The Pump That Started by Itself
The No. 2 hold bilge pump’s control rung: the series string, the hold-in and Hand in parallel. Then a pump running with the well dry and one that won’t run, each found with the meter.
Lesson
Shaft Generators: The Engine Doesn’t Care About 60 Hz
A sister ship with a shaft generator: slow the engine and watch the converter hold 60 Hz, set the condenser’s AVR, short a reefer feeder, then change over to the diesels before the pilot.
Lesson
Shore Power
Prove rotation and fix it at the shore end, judge four berths’ volts and hertz, fit the load under a 400 A pier breaker, change over through a blackout, see why a ground trips on shore power, and find a warm lug.
Lesson
Single-Phasing
The No. 1 LT pump loses a phase: watch it keep running and fail to restart, see why in the stator field, settle four calls with the clamp meter, and find the open with the ohmmeter.
Lesson
Solenoids, Limit Switches and Proxes
Prove a purifier’s solenoid valve with its LED, volts and ohms; change the coil; look at a hatch cover limit switch’s arm and cam before its contacts and set a new one; catch a PNP sensor on a card wired for NPN and set the gap; seven calls.
Lesson
Source to Load: Where Every Fault Lives
Every circuit is a source, a path and a load. On the No. 2 HT pump starter: a dead control transformer, an open coil and an open selector contact, each found by the three questions in order.
Lesson
Staying Alive: Lock-Out, Gas Tests, Hot Work and the Alarms
Make No. 1 SW pump safe: prove it dead, then block, bleed and prove zero on the sea side. Gas-test a double-bottom tank and read the permit, set up hot work on both sides of a bulkhead, find the hazards aloft, answer the alarms you must know, and decide go or don't go on eight jobs.
Lesson
Stored Energy and Arc Flash: Where It Hides
Four places energy stays after the breaker opens: an ACB’s closing spring, a drive’s DC bus, a pump turned by back-flow, a battery bank. Then the arc-flash label on the main board.
Lesson
Swap a Card, Force a Point, Back Up and Restore
No. 1 hydrophore pump’s PLC: back up before you touch, swap a dead output card with its block still wired, set a new card’s address, force a failed float and clear it, restore after a flat battery.
Lesson
Synchronizing and Load Sharing
Put No. 2 generator on the board: match voltage and frequency, close just before 12 on the synchroscope, share the kW with the governors and the kVAR with the AVRs, fix a backward droop CT, and sort six sets that won’t share.
Lesson
Tanks and Soundings: The Tape Decides
Inside a double-bottom tank; take a sounding and check the reference height; sounding or ullage; table, trim and temperature to metric tons; tape against the TLI and the dead band; a painted vent at bunkering; five tank calls.
Lesson
The 4–20 mA Loop: Read It, Find the Break, Prove It
Read the milliamps before you climb the tank, read DG2’s LO pressure loop at every terminal, go card first, half-split a dead tank loop with volts across the pair, prove it with 4, 12, 20 mA.
Lesson
The Alarm Is a Symptom
DG1’s HT outlet alarms at 97 °C on two nights: one false, found with the thermometer and a neighbor; one true, walked round the HT circuit to a three-way valve stuck on bypass.
Lesson
The Alarm System as a Map
Climb the alarm system from a sensor to the cabin panel; put an unmanned night in order; read an alarm point list; find why an alarm never came (a block signal stuck on); inhibit, un-inhibit and the point someone forgot; where alarm ends and control begins; five calls.
Lesson
The Alternator in One Line: Two Loops, Three Machines and a Box
DG3 opened up: the power path from the PMG to the bus, the AVR’s loop working on a load step, the maker’s AVR sheet read part by part, a day-one walk round, and why you never megger through the AVR.
Lesson
The Bow Thruster
The biggest motor on the board: whose parts are whose, why it never starts across the line, the start permit (all three sets, lever at zero), megger before the port, and the clamp on the first start.
Lesson
The Control Schematic
MAC1’s starter on one control schematic: tap the eight loads, read back from the M coil, see what drawn de-energized means when running, find K2’s contacts by name, then find why it won’t start in Auto.
Lesson
The Emergency Generator Chain
Watch the undervoltage relay open the tie, start the 250 kW set and close its breaker inside 45 seconds; sort the emergency board’s loads; check cranking volts; run the real test with the tie open and the load on; and name six quiet failures.
Lesson
The Fire Detection Panel: Loops, Addresses, Interlocks
Where Hawsepiper’s fire panel, relay unit, battery and feeds are; addresses on loop B; a drilled cable lost as a range between two isolators; what the panel stops and releases (never the CO₂).
Lesson
The Frequency Meter Test: Which Loop Is Sick
On any generator complaint, look at the frequency meter first. Steady: the AVR side. Swinging or wrong: the engine side. Five complaints, each half walked, and what changes when two sets are paralleled.
Lesson
The Galley
Ranges and their hotplate selectors, the oven and combi oven, the fryer and its high limit, the dishwasher, and the boiling pan (a steam-jacketed kettle): what each does, the core parts, and the faults you will be called for.
Lesson
The Half-Split
Find an open among sixteen points in four readings by testing the middle of what is left, find the masthead light’s open using only the boxes you can reach, and four calls on where to read next.
Lesson
The Induction Motor: Slip, Starting Current, Torque
Why the rotor never catches the field, and how to read a motor’s load off a tach when the ammeter is dead. Then six to eight times on start, and torque with the square of the volts.
Lesson
The Laundry
Washers (door lock, heater, drain pump, inverter motor), the dryer (heater, airflow switch, high limit, lint) and the laundry GFCI: what each part does, and the calls you get on a Sunday.
Lesson
The Loop Drawing
DG2’s LO pressure, GE221, on its own loop sheet: follow it from transmitter to card, mark the test points in order, read the scale, half-split a dead loop at the test points, and find a loop with no sheet.
Lesson
The Main Board One-Line
What each feeder on the main board protects, what else just lost power, inside a feeder cubicle, a crane feeder trip walked down to a wet junction box, why an open tie proves nothing, and six calls.
Lesson
The Nameplate and the Overload
Read the LT pump motor’s plate, clamp its amps against it, link the box for 440 V, work out a painted-over plate, then match a contactor and overload, set the dial and sort five motors that keep tripping.
Lesson
The Nav Sensors and the Feeds Between Them
Who talks to whom through Hawsepiper’s data distributor; read the sentences on a laptop; GPS 1 sending “no fix” traced up its antenna cable; transducer before display; two ECDIS that must match.
Lesson
The PLC and What Its Lights Mean
No. 1 hydrophore pump on a PLC: find the power supply, CPU, cards and port; read the LEDs through a good cycle; four mornings split by the lights; an input proved with the meter; five calls.
Lesson
The Radar as Blocks: Scanner, Magnetron and Inputs
Radar S on M/V Hawsepiper, block by block: one pulse round the set, a magnetron fading over six log pages, four wrong pictures traced to their block, and what on it is electrical.
Lesson
The Ship’s Networks
Take a network switch down and see why there are two; measure and fix the resistors on an RS-485 Modbus chain; three silent devices (address, baud, polarity); a switch’s lights for power, cable or a duplicate IP; fiber tested with light; six calls.
Lesson
The Synchronous Machine: Two Sets of Rules
The same governor and AVR knobs on a set alone and on a set paralleled. The helper who raised the voltage, the set that motored, and six which-rules calls.
Lesson
The System Wiring Diagram
DG1’s cubicle on sheet E-201: trace a phase from source to load, the CT loop through the ammeter and the 51 relay, the PT and its blown fuse, and the 110 V DC trip circuit; then find why the breaker didn’t trip with a meter, in two rounds.
Lesson
The Three-Wire Starter
Build a motor starter's control circuit one part at a time, see why it holds itself in and why it stays out after a blackout, then find the fault in a dead one with a meter.
Lesson
The Troubleshooting Method on One Page
The ETO book's Part 8 moves in one short lesson. Before you open the box, source to load, the half-split, voltage drop, load and prove the meter, one fault at a time, when to stop and call, and one practice fault on the No. 1 LT pump.
Lesson
The Ungrounded System: The Ground That Waited a Week
Why Hawsepiper’s 440 V has no link to the hull: the first ground trips nothing, moves the hull and not the phases, and waits. Then two grounds make a short.
Lesson
The VFD from the Outside
The ER exhaust fan’s drive: rectify, store, chop; the DC bus that outlives the power; the six parameter groups you touch; rotation at the motor leads; six fault logs; and the insulation alarm that comes with the bow thruster.
Lesson
Transformers and the 220 V Side
Two transformer banks on two halves of the board and the interlocked changeover, half the volts and twice the amps, why a 220 V ground never shows on the 440 V lamps, a hot transformer checked in order, taking a bank out of service, and six calls.
Lesson
Transmitters and Switches
A number or yes or no; change a pressure transmitter on its valve and vent, and the standby it starts; four tanks where level lies by type; a flow switch that says no flow; set and differential on the air compressor; the path before the loop.
Lesson
Troubleshoot a Battery Charger
Hawsepiper’s engine room 24 V charger, CH2, opened up: door meters first, then four faults: a blown input fuse, a latched board and a cooked output fuse, a sense lead adrift, an open diode.
Lesson
UPS Systems: Online, Line-Interactive, Bypass
UPS-1 under Hawsepiper’s alarm system: its path, battery and bypass, what a line-interactive unit lets through, the loads nobody designed for, and the battery that failed its test.
Lesson
Using a Meter
Volts AC and DC on an insulated ship, proving dead live-dead-live, continuity and ohms on dead circuits, the door ammeter and the clamp, and the megger at 500 V, on the No. 1 LT pump starter.
Lesson
Valves: Open, Shut, and Holding
Parts on a globe cut open; open or shut on seven valves; six valve types on the SW pumps and which you may throttle; symbols and the legend rule; the standby turning backwards; proving isolation past a slipped gearbox pointer; five calls and who does which job.
Lesson
VDR, Nav Lights and the Whistle
A VDR alarm traced to a wet wing microphone, the departure test of every nav light on both lamps, a sidelight found by lamp, gasket, panel and ohms to hull, and a silent whistle.
Lesson
Vocabulary: The Words on Day One
About forty electrical words you meet on your first day, learned by tapping the parts of a starter, the ship's power, a set of cards and a ladder rung, then a quick match.
Lesson
Voltage Drop Across a Contact
Measure across each closed pole of the running LT1 contactor and find the pitted one dropping 14 V, work out the heat, see why it only shows under load, and sort six readings from a panel round.
Lesson
Watertight Doors, Davits and the Boat Battery
A WT door that shows open on the bridge while it is shut, a davit limit that didn’t stop the hoist, a lifeboat battery dying behind a green davit plug, and a lift’s safety string.
Lesson
Weld a Bracket, Cut a Seized Nut
A new pipe bracket on M/V Hawsepiper, start to finish: what not to weld, the hot work permit walk on both sides of the steel, the rod and the amps, the fillet and four beads read, then the gas set up, lit, cut with, shut down, and a flashback.
Lesson
When to Stop, When to Call, How to Hand It Over
Radar S’s display is dead. Prove the outside with a meter, swap in the spare, read code 17 and stop at the processor. Then the call that gets a part, and the handover the next person starts from.
Lesson
Windlass, Mooring Winches and Hatch Covers
MW3, the port aft mooring winch: what is electrical on deck, two speeds and two overloads, a motor that hums against its brake, rain in the control station, and No. 2 hatch cover held by its own limit.
Lesson
Wye-Delta Starting
A step-by-step lesson on wye-delta starting: why it exists, the six winding ends, the three contactors, setting the timer, what it can't start, and a fault to find.
Worksheets
(8)
Worksheet
Ten Questions
Worksheet. Match the ten questions to the sheets that answer them, answer all ten for M/V Hawsepiper without a drawing, find the one no sheet answers, and see which sheets to walk again. Then keep your own ten at the front of your turnover notes.
Worksheet
The 45 Seconds
Worksheet. Build M/V Hawsepiper’s blackout timeline from the moment the bus dies: the relay, the interconnector, the start, the bank, the breaker at 13 s. Sort what comes back by itself, then the standby set and the sequential restart, and the steering pump that didn’t come back. Then fill in and print your own.
Worksheet
The Battery Register
Worksheet. Find all twelve of M/V Hawsepiper’s batteries, from the emergency generator’s starting banks to the boiler controller’s memory cell, and put them on one page; read it for the oldest, the charger showing no current and the banks never tested on load; judge three load-test curves. Then fill in and print your own.
Worksheet
The Bridge Table
Worksheet. Walk M/V Hawsepiper’s wheelhouse and radio station and write every box’s breaker, UPS, data in, feeds, antenna and owner; then the gyro that loses power, six jobs sorted into yours and the contractor’s, and three calls. Then fill in and print your own.
Worksheet
The Cabinet Map
Worksheet. Mark M/V Hawsepiper’s alarm system cabinets and the makers’ controllers on a plan, with what each reads, what feeds it and its network; sort the inhibits and forces into explained and ask-the-engineer-in-charge; then the twenty alarms from the purifier room. Then fill in and print your own.
Worksheet
The Islands and the Control Power
Worksheet. Walk M/V Hawsepiper’s ground lamps and insulation monitors, AC and DC, and note today’s readings; answer four ground alarms from the sheet; fill in the four control supplies; find the dark panel’s fuse. Then fill in and print your own.
Worksheet
The Megger Log
Worksheet. Write the line (date, frame temperature, one-minute reading), plot five of M/V Hawsepiper’s motors over a year, bring them to the same temperature, and sort the steady, the wet, the falling and the one that only got warm. Then start your own log.
Worksheet
Your Own One-Line
Worksheet. Walk M/V Hawsepiper’s two switchboards door by door, check your sheet against the yard one-line, settle each difference at the door, mark the halves, then fill in and print the sheet for your own ship.
Simulators
(40)
Simulator · free play
Battery Charger
Float, boost and temperature compensation on a 24 V lead-acid bank, reading cell voltages and specific gravity, and finding out why a charger isn't charging.
Simulator · free play
Blackout Drill
Overload a generator and watch preferential trip and the standby start; black out the ship and follow the emergency generator, bus tie and sequential restart against the 45-second clock.
Simulator · free play
Breaker Won't Close
An air circuit breaker that won't close: read its flags, measure its coils and find which of eight interlocks or faults is stopping it. Then rack one out in the right order.
Simulator · free play
Brushless Alternator
Follow a brushless alternator's excitation chain from PMG to main field, test the rotating diodes with a meter, and diagnose six excitation faults.
Simulator · free play
Central Cooling
A ship's central cooling system: sea water, LT and HT fresh water circuits and their three-way valves. Change the load, then find the fault.
Simulator · free play
Crane Control
Fault-find an all-electric crane hoist's control: emergency stops, limit switches, the overload limiter, hoist contactors and the spring-applied brake, with a meter on the ladder diagram.
Simulator · free play
Electro-Hydraulic Deck Crane
Deck crane CR1, electro-hydraulic, 25 t: a wye-delta pump motor, the hydraulic power unit, a PLC with its lights and diagnostic page, valve coils, limits, the SWL limiter and the slip rings. Take a fault, find it with the meter, fix it and prove it.
Simulator · free play
Engine Safety System
Main engine alarms, slowdowns and shutdowns: push the sensors past their limits, cancel from the bridge, find out what can't be canceled, and what a broken sensor wire does.
Simulator · free play
Fault Bench
Starters with a fault you cannot see: operate them, read volts, ohms and amps on any terminal, find the fault, fix it and prove it. Twelve circuits (across-the-line pump, hold bilge pump on floats, wye-delta, a standby pump that starts on low pressure, a starting air compressor with its unloader and trips, and the sewage plant three ways: on floats with its blower, and two timer-run plants; the engine room crane hoist, reversing, with its limits and brake; a generator breaker's closing and tripping circuits in TEST; and an alarm system cabinet with two 4–20 mA loops and two switch inputs; and a hydrophore pump run by a PLC, where the program is your meter) and 250 faults at random.
Simulator · free play
Firing Order
See a six-cylinder marine diesel's firing order: crank throws from the end, pistons from the side, and which unit is on its power stroke.
Simulator · free play
Follow the Wire
Chase a hold bilge pump fault through a schematic, a terminal diagram and a cable list: sheet-and-column cross-references, wire numbers, terminal strips and cable numbers.
Simulator · free play
Fresh Water Generator
Start and stop a jacket-water-heated vacuum fresh water generator step by step, watch the vacuum and boiling point, and diagnose nine common faults.
Simulator · free play
Gauges to Diagnosis
Turn refrigeration gauge and thermometer readings into superheat, subcooling and a ranked list of likely faults.
Simulator · free play
Generator Protection
Read the trend before a generator trip and name the protection that operated, then set a generator breaker’s overcurrent curve so it rides through a motor start but still discriminates with the feeders.
Simulator · free play
Governor Knobs
The four knobs on a Woodward UG-type governor, live on a 750 kW generator: speed setting, droop, load limit and compensation. Stop the hunting, set 3% droop, and see the 2301A equivalents.
Simulator · free play
Ground Hunt
Read the ground lamps and insulation monitor on an ungrounded ship's system, hunt a ground breaker by breaker, and tell a ground from a short or an open.
Simulator · free play
Indicator Card Lab
Read slow-speed diesel indicator cards: compare units, spot the bad one and name the fault.
Simulator · free play
Induction Motor
Torque, current and slip of an induction motor as the load and voltage change, how to read the nameplate and set the overload, and how to prove a single-phased motor.
Simulator · free play
Ladder Logic
Read a live ladder diagram for the No. 2 cargo hold bilge pump with Hand-Off-Auto, a seal-in, an overload, a run timer and a silenceable alarm, then fix five broken rungs.
Simulator · free play
Line It Up: Fuel Oil
Line up a ship's fuel oil transfer and purifier system valve by valve, then find the fault in a bad lineup.
Simulator · free play
Loop Check
A 4–20 mA loop from supply to card: scale the signal, find the break with a voltmeter, and run a five-point transmitter calibration with as-found and as-left.
Simulator · free play
Motor Starter Fault Hunt
Troubleshoot a three-phase motor starter with a virtual meter: find where the voltage stops and name the fault.
Simulator · free play
Parallel the Generators
Bring a ship's second diesel generator onto the board: match voltage, watch the synchroscope, close the breaker and share the load.
Simulator · free play
PID Tuning
Tune a jacket-water temperature controller: gain, integral and derivative on a live loop with load changes, a hunting as-found setting and a sticky valve.
Simulator · free play
PLC Programmer
Learn to write ladder logic from zero. Follow along: twenty-two short guided exercises that tell you exactly what to press, from what a PLC is to contacts, coils, branches, the seal-in, NC wiring, the scan, memory bits, timers, latches, counters, the one-shot, alarm logic, numbers and math, 4–20 mA scaling, an analog alarm with a deadband, a step sequence, and the watch and force tables; skip any you know. Then build it yourself: eleven jobs on the ship's machinery, from a starter and a hold bilge pump to wye-delta, run hours, a hydrophore on a pressure transmitter, tank level alarms with a sensor fault and MAC1's auto start sequence, each checked by tests.
Simulator · free play
PLC Rack
Sinking and sourcing inputs with PNP and NPN sensors, reading a PLC rack's LEDs to split a fault between field and PLC, and the safe order for swapping a card or forcing a point.
Simulator · free play
Provision Plant
Run a ship's provision refrigeration plant with three rooms, pump-down control and a live control ladder, then diagnose eight common faults.
Simulator · free play
Pump Lab
Start a centrifugal pump the right way, compare it with a positive displacement pump against a closed valve, and see why two pumps in parallel don't double the flow.
Simulator · free play
Purifier Gravity Disc
See how oil density, temperature and gravity disc size move the oil-water interface in a purifier bowl.
Simulator · free play
RTD and Thermocouple
Pt100 resistance and lead-wire errors in 2, 3 and 4-wire circuits, type K thermocouples with cold junction and the wrong extension wire, and a temperature sensor fault hunt.
Simulator · free play
Shore Power
Take the ship onto shore power: check voltage, frequency and rotation, cut the load to what the shore breaker can carry, transfer, and recognize the expected ground.
Simulator · free play
Starting Air
Line up, blow through and start a two-stroke main engine on 30 bar air, see why air start valves overlap, and diagnose seven starting air faults.
Simulator · free play
Steering Gear
An electro-hydraulic steering gear with two power units: steer it, run the SOLAS swing test, and handle a leak, a trip and a follow-up failure.
Simulator · free play
Switchboard Meters
kW, kVAR, kVA, amps and power factor on the generator panel: build the load and watch the power triangle, then read two paralleled generators and fix uneven kW and kVAR sharing.
Simulator · free play
The Meter
Pick the right tool, dial position and jack for 16 ship jobs, see phantom voltage and LoZ, find a burnt contact by voltage drop, and put prove-dead in order.
Simulator · free play
Three-Phase
Rotating phasors and sine waves, RMS and peak, wye and delta line and phase values with practice problems, and phase rotation: why swapping two leads reverses a motor and three don't.
Simulator · free play
Timing Wheel
Turn the crank and see valve, port and injection timing on two-stroke and four-stroke marine diesels.
Simulator · free play
Two-Stage Air Compressor
Run a two-stage starting air compressor and diagnose leaking valves and fouled coolers from stage pressures and temperatures.
Simulator · free play
Variable Frequency Drive
Inside a VFD: rectifier, DC bus and PWM inverter. See the harmonics a drive puts on a ship’s bus, set one up from a motor nameplate, and work out why it tripped.
Simulator · free play
Wye-Delta Starter
Start a motor across the line, wye-delta, soft-start or by autotransformer and compare the current, find the fault in a wye-delta starter, and set a purifier’s overload bypass timer.
Tools
(7)
Tool
Engine Room Flash Cards
Learn the proper name and the shop name for everything in the engine room, with spaced repetition.
Tool
Glossary Flash Cards
All 1,319 words in The Practical Marine Engineer’s glossary as flash cards: decks by learning stage, by chapter or A–Z, either side first, knew it / not yet with spaced repeats, and a search.
Tool
PT Chart Trainer
Read a refrigerant pressure-temperature chart from a gauge, then drill it against the clock.
Tool
Symbol Dialects
The same motor starter drawn the US way, the European IEC way and the way Japanese and Korean yards label it. Name the symbols and decode the tags.
Tool
Weld Test Positions
How to run 1F to 4F six-pass fillets and 1G to 4G groove test welds with stick: plate position, where every bead goes and how to angle the rod for it.
Tool
Welding Shop Lookup
Set up a weld: pick the metal, thickness, position and joint and get the rod, size, amps, polarity, lens shade, preheat and fit-up. Decode any rod or wire number, identify the metal by magnet, spark and file, estimate hardness, and keep the bench charts.
Tool
Welding Symbol Builder
Build a welding symbol piece by piece and see what it means: arrow side, other side, size, contour, field weld and the joint it describes.
The ship
(2)
The ship
One-Line Diagram
A ship's distribution as a one-line diagram: open any breaker and see what goes dead, trace a user back to its source, and name the breaker from the symptoms.
The ship
Walk the Engine Room
A clickable plan of a motor ship's engine room: what each machine does, what to check on rounds, and the practice app for it.