No return path. On an ungrounded (insulated) system nothing connects any phase to the hull on purpose. A ground on one phase just pulls that phase to hull potential. With nowhere for current to go back to, nothing flows that a breaker would notice.
The lamps are a voltmeter. Each lamp sits between one phase and the hull. Healthy, they each see phase-to-hull voltage (about 254 V on 440 V), so they glow the same. Ground phase A and lamp A sees nothing, while B and C see the full 440 V line voltage and go bright.
Why it still matters. The two healthy phases are now 440 V above the hull, so a second ground on either of them is a phase-to-phase short through the ship’s structure. That trips, and it might trip something you need.
Each island has its own lamps. A transformer isolates its secondary, so a ground on the 220 V side shows on the 220 V lamps, never the 440 V ones. The emergency board, while it’s fed through the bus tie, is part of the 440 V island.
Simple resistive model. Real systems also leak through cable capacitance, which makes the shift a little softer.