Orange wire has power. A green fill between the plates means that contact is closed right now. A slash marks a normally closed contact.
Rails and rungs. Power comes from the left rail (L1) and has to find a closed path through the contacts to reach the coil on the right. Rungs are read top to bottom.
NO and NC. A normally open contact (two plates) closes when its device is actuated. A normally closed one (with the slash) opens. “Normally” means the device on the shelf, not how the plant usually runs.
Same name, same device. A coil called M drives every contact called M. That’s how rung 1’s M contact seals the pump in, and how the timer’s T1 contact sets the alarm.
Seal-in. The pump starts when the water reaches HIGH. Its own M contact, wired around LS-HIGH, keeps it running after the water falls below HIGH, until LS-LOW opens.