Rectifier. Six diodes turn 440 V three-phase into DC. The capacitors charge to the peak of the line voltage: 440 × √2 ≈ 620 V with no load, about 594 V running.
DC bus. Big capacitors smooth it. They hold that voltage after the drive is switched off: wait the time on the warning label (often 5 to 15 minutes) and measure the DC bus yourself before you touch anything inside.
Inverter. Six IGBTs switch each motor lead between the + and − of the bus thousands of times a second. The wider the pulse, the more voltage. Vary the pattern sinusoidally and the motor’s inductance turns the pulses into a near-sine current.
Volts per hertz. To keep the motor’s magnetic flux right, voltage rises with frequency: 440 V ÷ 60 Hz = 7.3 V per Hz. Above 60 Hz the drive has no more volts to give, so torque falls off.
The real carrier is far faster than drawn: at 4 kHz there are 67 pulses in every 60 Hz cycle.