| US | IEC | Yard |
|---|
The circuit never changes. Stop in series, start in parallel with a seal-in contact, coil, overload contact. Find those four on any drawing and you can read it.
US ladder: rungs run left to right between two rails, numbered down the left. The numbers on the right of each coil list the rungs where its contacts are (underlined for normally closed).
European IEC: current paths run top to bottom, the sheet is divided into numbered columns, and each coil has a little table beneath it saying which column each of its contacts is in. Every device is tagged with a letter: -K for relays and contactors, -S for switches, -F for protection.
Japanese and Korean yards mostly draw IEC-style symbols (Japan’s JIS C 0617 follows IEC 60617), but tag devices with JEM device numbers: 52 for a breaker, 88 for a motor contactor, 49 for the thermal overload. NO contacts are “a contacts”, NC are “b contacts”. Older drawings may use the earlier JIS shapes.
Lamp colors: on US and Japanese/Korean boards red usually means running or closed and green means stopped or open. European machinery often uses green for running. Check the legend sheet before you trust a color.