100 Ω at 0°C, rising about 0.385 Ω per degree: 119.4 Ω at 50°C, 138.5 Ω at 100°C. Disconnect it and read it with your meter: that’s the quickest test there is.
Lead resistance adds to the reading. In a 2-wire circuit both leads are in series with the sensor: every 0.385 Ω of copper reads as one degree hot.
3-wire uses the third lead to measure and subtract the lead resistance. It works if the leads match; a bad terminal on one lead brings the error back.
4-wire feeds current down one pair and measures voltage on the other: no lead error at all.