Click a test point for the red probe, then another for the black. Readings are DC volts.
Live zero. 4 mA means 0% of range. 0 mA means something is broken: a wire, a fuse, the transmitter. If 0% were 0 mA, a cut cable would read “tank empty” and nobody would know.
Power and signal on the same two wires. A two-wire transmitter runs on the few milliamps below 4, and sets the loop current to say what it measures.
The card reads volts. The 250 Ω input resistor turns 4–20 mA into 1–5 V. That’s why you can read the loop with a voltmeter across the card input without breaking anything: volts ÷ 250 = amps.
Out of range means fault. Most systems treat below about 3.6 mA or above about 21 mA as a failure (the NAMUR NE 43 convention), not a reading.
No current, no drop. With the loop open, every healthy wire and terminal reads 0 V across it, and the whole 24 V appears across the open. Half-split it: check the middle, then the half that’s still showing voltage.
Healthy, the voltage gets used up in two places: across the card’s 250 Ω (1–5 V) and across the transmitter (the rest, which must stay above its minimum, often around 10–12 V).
A minus sign means something. Polarity matters on a loop.
Hand pump and test gauge on the transmitter, meter in the loop. Tolerance here: ±0.5% of span (±0.08 mA).