Provision Plant

One compressor, three cold rooms, and a pump-down control system. Room thermostats open the room solenoids; the low pressure switch starts and stops the compressor. Watch it cycle, push it around, then find out why it’s misbehaving.

Refrigerant circuit · R-404A

Red is hot gas, tan is liquid, blue is suction. Gauge pressures, with the saturation temperature in brackets.

Control ladder

Orange is live. HP and OP are manual-reset trips; LP resets itself. DT is the defrost timer.

How pump-down works

Rooms don’t start the compressor directly. A room thermostat only opens that room’s liquid solenoid. Refrigerant flows into the coil, suction pressure rises, and the LP switch cuts in and starts the compressor.

Pumping down. When the last room is satisfied its solenoid shuts, the compressor pulls the suction side down to the LP cut-out and stops, with the refrigerant stored in the condenser and receiver. The master solenoid shuts with the compressor.

Why bother? No liquid sits in the coils or the compressor crankcase while it’s stopped, so it never starts on a slug of liquid or diluted oil.

EPR valves on the veg and dairy coils hold their evaporating pressure up so those coils stay just below freezing, and don’t freeze the stores or dry them out, while the meat room coil runs at about −28°C.

Rooms

Machinery
OFF