ETO · Part 0 · Drawings, and Part 3 · Distribution

One-Line Diagram

The whole ship on one sheet: generators, main board, transformers, the emergency board and the users hanging off them. Open breakers and watch what goes dead, then trace users back to their source the way you will when something goes dark.

440 V 60 Hz, three-phase, insulated neutral

Filled square: breaker closed. Hollow: open. Click a generator to start or stop it.

What’s live

    Reading a one-line

    One line stands for three. Every line is a three-phase circuit; the drawing shows what feeds what, not how it’s wired.

    It’s a tree. Generators feed the main board, the main board feeds transformers and big motors, the 230 V board feeds panels, panels feed loads. The key distribution plan is the same tree drawn as a list of boards and circuits.

    Work from the dead load back to its source. The first breaker you find open, or the first point where you lose voltage, is your fault. If several things are dead, find where their paths join: that’s where to look.

    The emergency board normally runs off the main board through the interconnector. Lose that, and the emergency generator starts and takes the emergency board on its own.