The field turns at synchronous speed: 120 × 60 Hz ÷ 4 poles = 1800 rpm. The rotor always runs a little slower; that difference, the slip, is what induces the rotor current that makes torque.
Slip grows nearly in step with load. So a tachometer on a pump motor tells you roughly how hard it’s working: 1796 rpm is idling, 1770 is about full load, 1740 is overloaded.
Current tells you less than you think at light load. An unloaded motor still draws a third of its full-load amps just to magnetize itself. That’s also why its power factor is poor.
Low voltage hurts. Torque falls with the square of voltage, so at 90% volts the motor slips further and draws more current to carry the same load: it runs hotter.
Starting: 6 to 8 times full-load current until it’s near speed. Past the breakdown point the motor stalls and the current goes straight to locked-rotor value.