ETO · Part 0 · Tools, and Part 1 · Theory with a meter

The Meter

Every position on the dial, which jack the red lead goes in, and which tool you should have grabbed instead. Then the three meter lessons that save the most time and skin: phantom voltage, voltage drop across a bad contact, and proving dead in the right order.

The job
0 of 0

Grab
Three rules for the leads

Black lives in COM. Only the red lead moves.

The A and mA jacks are a short circuit. They go through a shunt of a fraction of an ohm. Leave the red lead there, set the dial to volts and touch 440 V, and you’ve put a dead short across the bus through your meter. The fuse inside is all that stands between you and the arc. That’s what CAT ratings (CAT III, CAT IV) and proper meter fuses are for.

Current measured directly goes in series. You break the circuit and the meter becomes part of it. On anything bigger than control current, use a clamp.

Multimeter

Click a dial position, then the jack for the red lead. MIN/MAX and Hz are buttons above the dial.