ETO · Part 4 · Motors

Wye-Delta Starter

A big motor started straight on the line takes six to eight times its running current and dips the whole board. Compare the ways round that, hunt down the usual wye-delta faults, and set a purifier’s overload bypass so it starts without cooking the motor.

37 kW pump motor · FLA 61 A
t = 0.0 s
Starter
Load
The dashed line is your last start, for comparison.

Wye-delta power circuit

KM is the main contactor. KS makes the wye point; KD connects the windings in delta. KS and KD must never be in together: they’re interlocked electrically and usually mechanically too.