A motor running on two phases growls instead of hums, runs hot, and will not start from rest; one already running keeps turning on two phases at much higher current, about 1.7 times its normal amps on the two live lines, and up to twice, until the overload takes it off. The clamp meter settles it in thirty seconds: three phases roughly equal is healthy; one at zero and the other two high is single-phasing. Then find the open: a blown fuse in the starter, a contactor pole burned open, a loose lug, a broken lead at the gland, a failed conductor in the cable; less often, a breaker pole upstream of the starter or a broken lead inside the motor's terminal box. Work from the starter toward the motor with the circuit isolated, continuity on each phase.
The reason to understand this one properly is that the first symptom is often somewhere else. A starter whose overload trips every few days, a motor that runs hot, a breaker that trips on a start: single-phasing is on the list for all three, and the clamp meter is the test.
Pocket rules. Growl, not hum. Clamp all three phases first. Zero on one is the answer. The open is usually between the fuse and the gland; if that tests through, look upstream of the starter and at the motor's own leads. Find it with continuity.