4.18How motors break

Slide the drawing sideways, or open it full size.
Where motors fail
Figure 4.18. Where motors failOpen full size

Will not start, nothing happens. Control circuit: 4.5. Check hand/off/auto first.

Hums, will not turn. Single-phasing (4.3) or mechanically stuck or a brake not releasing. Clamp the three phases.

Starts and trips on overload. Motor amps against nameplate. High: the load, a bearing, single-phasing, low voltage. Normal: overload set wrong, class wrong, or the overload itself tired.

Trips the breaker on start. Inrush meeting a breaker set tight, a star-delta changing over too early, or a short in the motor or cable: megger before the second try.

Runs hot. Load, ventilation, voltage, a dragging brake, or a winding going. Clamp and megger.

Runs, stops, runs. A loose connection in the control circuit, a tired aux contact, or a two-wire control device (pressure switch, float) doing its job.

Noisy. Bearings, a loose cowl, or single-phasing. Bearings feel it in the frame; single-phasing reads it on the clamp.

Megger low. Water, then age. 4.2.

Reversed after work. 4.10. It happens to everyone once.

Drive faulted. Fault log, then 4.8.