Every alarm you will ever answer comes through this system, so understanding it is understanding how the ship talks. At the bottom, sensors: pressure, temperature, level, flow, switches, and the status contacts off every starter and breaker. Their cables land in field junction boxes and run to cabinets full of I/O cards, which turn a 4–20 mA signal or a contact into a number. Process stations read the cards, compare against limits, and raise alarms; they are duplicated so one can fail. A network carries it to operator stations in the control room and on the bridge, to the printer, and to the extension alarm system that wakes the duty engineer at night. The engineer's call, the dead-man, the UMS acceptance: all of it is this system.
It also does control on many ships: pump changeovers, standby starts, the sequence that restarts the plant after a blackout. The line between the AMS and the control system is drawn differently by every maker; find out where it is drawn on yours.
When you take over, learn three things: where the cabinets are and which one holds which part of the ship; how to find a point on the screen and read its raw value and its limits; and how to inhibit a point for maintenance and un-inhibit it afterward, because an inhibited point someone forgot is a real alarm nobody will hear.
Pocket rules. Every alarm is a sensor, a cable, a card, a limit, in that order. Raw value before you believe the alarm. Inhibit and un-inhibit, and log it. Know the cabinets.
Yours or not. Sensors, cables, cards, power supplies, operator stations, printer, extension alarms: yours. The software and the control logic inside the process stations: vendor, with you able to read it.