4.5 · (F) A job you do with your handsTrace a dead control circuit

Slide the drawing sideways, or open it full size.
Tracing a dead control rung
Figure 4.5. Tracing a dead control rungOpen full size

The pump will not start. The breaker is closed, the motor is fine, the button does nothing. Black lead on the right-hand rail and leave it there. Red lead to point 1: control voltage. Step right one point at a time with a helper holding the start button. Voltage is present at every point up to the open; the first point where it disappears puts the fault between that point and the last live one.

Volts at 1, nothing at 2: control fuse. Volts at 2, nothing at 3: stop button, or a remote stop or emergency stop in series with it that somebody left pushed. Volts at 3, nothing at 4 with start held: the start button. Volts at 4, nothing at 5: overload contact; reset it, then ask why it tripped before you leave. Volts at 5 and no pull-in: measure across the coil; full voltage and nothing is a burned coil or a jammed armature. Starts but drops out on release: the auxiliary contact or its wiring, because everything else has just proved itself.

Faults cluster at the things that move: buttons, the overload, the aux contact. Fuses and wire come last because they fail least.

Pocket rules. Black lead on the right rail and leave it. Step right until the volts disappear. Hold start while you read. Drops out on release is the aux contact. Overload tripped: check the motor amps before you reset it twice.

Work it

Built for this entry. Lessons first, then the simulator for free play.

Comes up in

Other entries that send you here.

All of Part 4