1.2Series and parallel

The pump that started by itself

Slide the drawing sideways, or open it full size.
Series and parallel
Figure 1.2. Series and parallelOpen full size

Where you'll meet it. A cargo hold bilge pump starts with the well dry and runs until somebody notices. The control circuit is a float switch in series with the coil, so the coil should be dead with the float down. Open the box and there is a jumper across the float switch terminals, left from a test last hitch. A jumper is a parallel path, and a parallel path means the coil has a second way to get power. The reverse problem is the common one: a circuit that will not work has one open somewhere in a series string, and every contact in the string is a suspect.

The idea. Everything that must be true is wired in series: fuse, stop, overload, interlock, coil. One open anywhere, the string is dead. Anything that can happen for more than one reason is wired in parallel: two start buttons, a hold-in contact around a momentary one. Won't run: look for the open in the series string. Runs when it shouldn't: look for the parallel path, a welded contact, a jumper.

Used in: 4.4, 4.5, 8.1, 8.2.