4.4 · (R) Yours: something you are responsible forThe three-wire starter

Slide the drawing sideways, or open it full size.
The three-wire starter, power and control
Figure 4.4. The three-wire starter, power and controlOpen full size

Two circuits in one box. The power circuit is simple: a breaker or fuses, a contactor with three heavy contacts, an overload relay with three heaters or a current sensor, and the motor. The control circuit is where the logic is: the coil of that contactor, and everything in series with it that can say no. Press start, the coil pulls in, the three power contacts close, and the contactor's own auxiliary contact closes across the start button so the coil holds itself in after you let go. Press stop, or let the overload open, or lose control voltage, and it drops out and stays out. That auxiliary contact is the difference between two-wire control, where a switch or a pressure switch holds the motor in and it restarts by itself when power returns, and three-wire control, where it does not. Automatically restarting hold bilge pumps, sewage plant discharge pumps and ventilation fans are two-wire; anything that could hurt someone when it restarts is three-wire.

Around the basic rung you will find remote stops in series, interlocks from other equipment, a run lamp off another auxiliary, a hand/off/auto selector, and a remote start from the automation system in parallel with the button.

Pocket rules. Two circuits: power and control. The coil is the question; everything in series with it is a suspect. Aux contact in parallel with start means three-wire. Hand/off/auto: check which position it is in before you troubleshoot anything.

Yours or not. All yours.

Work it

Built for this entry. Lessons first, then the simulator for free play.

Comes up in

Other entries that send you here.

All of Part 4