4.2 · (F) A job you do with your handsMegger a motor and dry it out

Slide the drawing sideways, or open it full size.
Megger the motor alone, and dry it out
Figure 4.2. Megger the motor alone, and dry it outOpen full size

Isolate at the starter, lock out, prove dead at the terminal box. Disconnect the motor leads from the supply leads, because you want the motor alone, not the cable and the contactor with it. Join the three motor leads, megger from them to the frame at 500 V, hold for a minute, read. If all six winding ends come out to the box, lift the links and megger each winding to the other two, to catch a phase-to-phase fault; with only three leads the windings are joined inside and that test is not possible. Record the figures and the temperature of the frame. Insulation resistance roughly halves for every 10°C the winding warms, so compare readings taken at similar temperatures; a motor colder than the air around it can sweat and read low.

Under two megohms it does not run. Wet windings dry out: heat lamps or a small heater in the terminal box with the lid propped, or a low-voltage current through the windings from a welding set in the hands of someone who has done it, frame temperature held under about 80°C, megger every few hours and watch the reading climb. A motor that climbs to tens of megohms and holds was wet. One that climbs, then falls when it cools, has insulation that is ending and should be scheduled out. One that will not climb at all has a winding fault.

Afterward: discharge the winding, reconnect, confirm the links, check rotation if you touched the leads.

Pocket rules. Motor alone, leads disconnected. One minute, write it down with the temperature. Two megohms is the floor. Dry, re-test, then run. Discharge after megger.

Work it

Built for this entry. Lessons first, then the simulator for free play.

Comes up in

Other entries that send you here.

All of Part 4