1.6The induction motor: slip, starting current, torque

The tachometer as a load gauge

Slide the drawing sideways, or open it full size.
Slip as a load gauge
Figure 1.6. Slip as a load gaugeOpen full size

Where you'll meet it. A fire pump motor's ammeter is dead and the pump does not seem to be delivering. You put a tach on the shaft: 1795 rpm on a motor whose nameplate says 1760 at full load. A 4-pole motor at 60 Hz would spin at just under 1800 with nothing on it, so 1795 means it is doing almost no work: a sheared coupling, a pump that lost suction, an impeller gone. Had it read 1700 it would be heavily overloaded, a bearing or a tight pump. Slip is a load gauge you can read with a tach when you cannot read it with an ammeter.

The idea. The stator field turns at synchronous speed, 1800 on four poles; the rotor chases it and never catches it, and the gap is slip, a few percent at full load and almost nothing at no load. Starting current is six to eight times full-load current, which is what overloads and breakers are sized to tolerate once. Torque falls with the square of voltage, so a motor on low voltage may start, draw high, and stall. A 50 Hz motor on 60 Hz runs 20 percent fast and its pump asks for far more than 20 percent more power; the nameplate matters.

Used in: 4.1, 4.3, 4.7.