1.7The synchronous machine

The helper who raised the voltage

Slide the drawing sideways, or open it full size.
The synchronous machine on a bus
Figure 1.7. The synchronous machine on a busOpen full size

Where you'll meet it. A well-meaning engineer paralleling a set notices the incoming voltage is a shade low and turns the voltage adjust up after the breaker closes, to help. The bus voltage barely moves. The incoming set's ammeter jumps, its partner's ammeter drops, and the kW meters on both sit where they were. He has not raised the voltage; he has moved kVAR from one set to the other, and if he keeps going he will circulate current between them that does nothing but heat both machines. Two minutes later the set he started trips on reverse power because he never raised the governor, and the breaker gets blamed.

The idea. Once a set is paralleled its speed is locked to the bus by the magnetic grip between rotor and stator. More fuel does not make it faster; it makes it take kW. More field does not raise the bus volts; it makes it take kVAR. Take the fuel away and it keeps turning in step, driven by the bus as a motor: reverse power, and the relay watching for it is protecting the engine. Alone on a dead bus the same machine's fuel sets frequency and its field sets voltage. Same machine, two sets of rules.

Used in: 2.1, 2.3, 2.4.