A big motor started across the line pulls six to eight times its running current and dips the bus. Reduced-voltage starting is the family of ways to soften that. Star-delta is the one you will see most: the motor's six winding ends are brought out, the starter connects them in star for the start so each winding sees only 58 percent of line voltage and draws a third of the current, then after a timed few seconds opens the star contactor and closes the delta contactor so the windings see full voltage and full torque. Three contactors, one timer, a motor with six leads, and a changeover that briefly removes power. Purifiers, big compressors and some pumps use it. Autotransformer starters do the same job with a tapped transformer instead of a reconnection, on motors with only three leads. Soft starters do it electronically, ramping the voltage with thyristors and then closing a bypass contactor so the thyristors do not run hot all day.
Two things about star-delta that confuse people. First, the overload is often in the delta leg, carrying winding current, which is 58 percent of line current; the overload is set to that figure, not to nameplate amps, and a replacement set to nameplate protects nothing. Second, on some starters, purifiers in particular, the overload is wired so it is bypassed or not in circuit during the star period, so a motor that stalls in star is not protected by the overload at all; the timer and the main contactor's own protection are all there is. Read the starter's own drawing, not a generic one. If a purifier starter keeps tripping on the changeover to delta, the motor is not up to speed when it changes over: a long start from a heavy bowl, or a timer set too short, or a weak star contactor.
Pocket rules. Six leads means star-delta. Overload in the delta leg is set to 58 percent of line current. Know whether the overload is in circuit during the start. Changeover trips: motor not up to speed.
Yours or not. All yours, including the timer and the soft starter's parameters.