1.5kW, kVAR, kVA and power factor

Reading the generator panel like a story

Slide the drawing sideways, or open it full size.
KW, kVAR, kVA on two generator panels
Figure 1.5. KW, kVAR, kVA on two generator panelsOpen full size

Where you'll meet it. Two sets on the bus. Set 1 reads 700 kW and 1400 A; set 2 reads 700 kW and 950 A. Most people see equal kW and walk on. The amps say the sets are not sharing kVAR: set 1 is carrying the reactive load for both and sitting near its current limit with no more kW on it than its partner. If the thruster starts now, set 1 trips on overcurrent and the engineers blame the breaker. The fix is inside the panel. On a board with manual control, nudge set 1's voltage adjust down and set 2's up until the amps meet, watching that the bus volts stay put. On a board with automatic sharing, the AVR droop pot or a reversed droop CT is the thing to look at. Same story for kW: when the auto load-share has died, you balance by hand with the governor raise/lower switches, watching the two kW meters and not the amps.

The idea. kW does work. kVAR builds and collapses the magnetic fields in every motor and transformer sixty times a second, does no work, and is current all the same. kVA is the two combined and it is what the ammeter reads. Power factor is kW over kVA. The engine is rated in kW; the alternator in kVA, which is amps. A ship full of half-loaded motors runs at a poor power factor, and a set can be at its ammeter limit with kW to spare. Governors split the kW; voltage regulators split the kVAR; two separate adjustments.

Used in: 2.1, 2.3, 2.9, 8.9.