The voltmeter selector switch
Where you'll meet it. You turn the voltmeter selector through its positions. Phase to phase: 450, 450, 450. Phase to ground: 230, 290, 260, and they drift. A new ETO decides the board has a problem. It does not. On an ungrounded system the phase-to-ground voltages are set by nothing but leakage and capacitance, and they wander. Only phase-to-phase means anything, until a ground pins one phase to the hull; then phase-to-ground reads 0, 450, 450 and the lamps go with it. Knowing which readings matter saves you an afternoon.
The idea. Nameplate voltage is between lines. Inside a wye-connected machine each winding sees line voltage over 1.73, about 260 V, which is what the stator insulation and your megger reading live with. In a delta each winding sees full line voltage. Rotation is the order the phases peak in, set by nothing but which conductor goes to which terminal; swap two and every motor downstream runs backward, which is why rotation gets checked after any cable work, every time.