3.6 · (R) Yours: something you are responsible forThe three ground lamps and the insulation monitor

Slide the drawing sideways, or open it full size.
Ground lamps, healthy and with a ground on B
Figure 3.6-1. Ground lamps, healthy and with a ground on BOpen full size

Three lamps on the switchboard, one per phase, wired from each bus to the hull. On a healthy ungrounded system all three glow the same dim orange. When one goes dark and the other two go bright, you have a ground on the dark phase. That is the whole instrument.

With no fault, the only path from any phase to the hull is through the lamps, wired in wye with their common bolted to the hull, so each lamp sees phase-to-ground voltage, about 260 V on a bus running at 450 V, and they share the glow equally. Put a ground on phase B and that fault shorts out lamp B; it goes dark. Lamps A and C now sit directly across line-to-line voltage, 450 V, and they go bright. Dark lamp tells you the phase; bright lamps confirm it.

The lamps cannot tell you how bad or where. For how bad, the board has an insulation resistance monitor that injects a small DC signal and reads the ohms to hull, alarming below a setpoint that is usually well under a megohm on the 440 V side; read yours off the monitor. For where, see 3.7.

Slide the drawing sideways, or open it full size.
The real IRM and ground lamp circuit
Figure 3.6-2. The real IRM and ground lamp circuitOpen full size

On a real board the three lamps are not wired straight across the phases. Each has a small transformer, 440 to 6.3 V, with the three primaries in wye and the star point bolted to hull, and the lamp on each secondary. The physics is identical to the bare-lamp picture, the lamps just live at a safer voltage. Beside the lamps, the insulation resistance monitor takes its supply from a 230 V control transformer, injects its own low-voltage DC signal between the system and hull, reads the ohms on a 0 to 5 megohm meter on the panel front, and closes an alarm contact to the alarm system below its setpoint. A ground test switch lets you prove the monitor by putting a known path to hull on it.

Pocket rules. One dark, two bright: ground on the dark phase. All three even: healthy, or a leak shared across the phases; the monitor's number says which. Lamps that never change, even on the ground test switch: the lamp common has lost the hull; fix the instrument before you believe it. On shore power the monitor reads the pier's grounded neutral and alarms, unless the ship takes shore power through its own isolation transformer; it clears when the shore breaker opens.

Yours or not. Lamps, monitor, the hunt and the repair: yours. A ground inside a sealed drive or a nav unit: find it, prove it, then call.