A feeder breaker trips on no load change. A fault downstream. Walk the cable and megger the load before you re-close; a second close onto a fault is how switchboards get damaged.
A breaker trips every start. Inrush meeting a breaker set too tight, or a fuse of the wrong speed, or a motor that has grown a problem. Compare the start current with the nameplate before you touch the setting.
Hot lug, smell of hot phenolic. A loose connection making volts under load. Measure across it (1.1), de-energize, and replace the terminal; do not just retighten.
Ground lamps uneven. Go to 3.6 and 3.7.
A whole panel dead at once. Control power. Find the control fuse or the DC supply before you suspect anything else.
Lights dim when a motor starts. Normal if brief. If it lasts, a loose connection in the lighting feeder or a transformer tap that does not suit the supply.
Nuisance preferential trips. Load over the line. Look at the kW trend and the generator schedule, not at the relay.
Everything on one half of the board behaves oddly. A tie breaker or a generator breaker not fully closed, or a bus connection going bad. Thermal camera on the bus connections at the first opportunity.