The switchboard is a page of numbers that most people walk past, and the numbers tell stories to anyone who reads them. Two sets, equal kW, one with far more amps: kVAR is not sharing, the AVRs and their droop. Unequal kW with the frequency sitting where it should: the governors, droop settings or setpoints or a load-share line. Frequency a touch low on both with the kW high: the plant is near its limit and the next big start will tell you. A set with its ammeter near the limit and its kW well under: poor power factor, and a thruster start will trip it. Volts a little low on the bus with all sets equal: the weight of a lot of reactive load, or the AVR reference on all of them. The panel is read in a glance once the stories are familiar, and the glance is part of every round.
Pocket rule. Equal kW and unequal amps is a kVAR story. Unequal kW is a governor story. Read the panel every round.