8.8The frequency meter test: which loop is sick

Slide the drawing sideways, or open it full size.
The frequency meter test
Figure 8.8. The frequency meter testOpen full size

On any generator complaint, look at the frequency meter first. Steady frequency with volts wrong, hunting or absent means the trouble is on the electrical side: AVR, diodes, sensing, excitation. Frequency swinging or wrong means the trouble is on the engine side: governor, fuel, load. One glance sorts the job between two loops that share a shaft and nothing else, and sends you, or the engineers, to the right half. Paralleled, watch the kW meter instead: the bus holds the frequency, and a hunting governor shows as kW swinging between the sets.

Pocket rule. Frequency steady: AVR side. Frequency swinging: engine side.