2.9How generation breaks

Slide the drawing sideways, or open it full size.
The frequency meter decides which loop is sick
Figure 2.9. The frequency meter decides which loop is sickOpen full size

Start at the frequency meter; it tells you which loop is sick.

Frequency steady, no volts. PMG machine: follow the chain outward, PMG output at the AVR, AVR fuse, AVR output to exciter field, field resistance, diodes, main field. No PMG: residual magnetism, flash it.

Frequency steady, volts low or hunting. AVR stability pot, sensing fuse, a loose sensing lead, then a shorted diode.

Frequency swinging. Governor, fuel, load. You own the pickup, the actuator wiring and the electronic governor box; check those, then hand it over.

Will not share kW. Droop settings, speed setpoints, a load-share line. Will not share kVAR, amps far apart with kW equal. AVR droop, and the classic cause is a droop CT wired backward after an AVR change.

Reverse power seconds after closing. Incoming set a touch slow. Closed out of phase. You will know; afterward, prove the check-sync relay before anyone synchronizes again.

Low megger. Moisture, and almost always a dead space heater nobody noticed because the set was running. Disconnect the AVR and diodes, dry it out, trend the reading up before you run.

Stator or bearing temperature climbing. Filters, cooler, or an unbalanced load; check the three phase currents before anything else.

Emergency set will not start by itself. Go back to the five links in 2.6 and test them in order.

Work it

Built for this entry. Lessons first, then the simulator for free play.

Comes up in

Other entries that send you here.

All of Part 2