A transmitter and its card are connected by two wires carrying 4 to 20 mA, with 24 V from the card or a separate supply driving it. The current is the same everywhere in the loop, which is the whole point: you can read it at the transmitter, at any junction box, or at the card and get the same number. The places you can get at it are the loop's test points, and the loop drawing (0.8) shows them. Where no loop drawing exists, the connection diagrams (0.4) will get you from card to transmitter one strip at a time.
Three readings, three meanings. Current flowing and matching the process: the loop is fine and the alarm is about the plant. Current flowing and not matching the process: the transmitter. No current: the loop is open somewhere, and you half-split it (8.2). Above 20 mA, or a steady reading just under 4: the transmitter is telling you it has failed.
Pocket rules. Same current everywhere. Read it at the easiest terminal, not the hardest. Open loop reads zero; a faulted transmitter parks just under 4 or above 20. Check the loop power before you blame anything in it.