5.2 · (R) Yours: something you are responsible forThe 4–20 mA loop and its terminals

Slide the drawing sideways, or open it full size.
One loop, every terminal
Figure 5.2. One loop, every terminalOpen full size

A transmitter and its card are connected by two wires carrying 4 to 20 mA, with 24 V from the card or a separate supply driving it. The current is the same everywhere in the loop, which is the whole point: you can read it at the transmitter, at any junction box, or at the card and get the same number. The places you can get at it are the loop's test points, and the loop drawing (0.8) shows them. Where no loop drawing exists, the connection diagrams (0.4) will get you from card to transmitter one strip at a time.

Three readings, three meanings. Current flowing and matching the process: the loop is fine and the alarm is about the plant. Current flowing and not matching the process: the transmitter. No current: the loop is open somewhere, and you half-split it (8.2). Above 20 mA, or a steady reading just under 4: the transmitter is telling you it has failed.

Pocket rules. Same current everywhere. Read it at the easiest terminal, not the hardest. Open loop reads zero; a faulted transmitter parks just under 4 or above 20. Check the loop power before you blame anything in it.

Work it

Built for this entry. Lessons first, then the simulator for free play.

LessonThe 4–20 mA Loop: Read It, Find the Break, Prove ItRead the milliamps before you climb the tank, read DG2’s LO pressure loop at every terminal, go card first, half-split a dead tank loop with volts across the pair, prove it with 4, 12, 20 mA.Simulator · free playFault BenchStarters with a fault you cannot see: operate them, read volts, ohms and amps on any terminal, find the fault, fix it and prove it. Twelve circuits (across-the-line pump, hold bilge pump on floats, wye-delta, a standby pump that starts on low pressure, a starting air compressor with its unloader and trips, and the sewage plant three ways: on floats with its blower, and two timer-run plants; the engine room crane hoist, reversing, with its limits and brake; a generator breaker's closing and tripping circuits in TEST; and an alarm system cabinet with two 4–20 mA loops and two switch inputs; and a hydrophore pump run by a PLC, where the program is your meter) and 250 faults at random.Simulator · free playPLC ProgrammerLearn to write ladder logic from zero. Follow along: twenty-two short guided exercises that tell you exactly what to press, from what a PLC is to contacts, coils, branches, the seal-in, NC wiring, the scan, memory bits, timers, latches, counters, the one-shot, alarm logic, numbers and math, 4–20 mA scaling, an analog alarm with a deadband, a step sequence, and the watch and force tables; skip any you know. Then build it yourself: eleven jobs on the ship's machinery, from a starter and a hold bilge pump to wye-delta, run hours, a hydrophore on a pressure transmitter, tank level alarms with a sensor fault and MAC1's auto start sequence, each checked by tests.Simulator · free playLoop CheckA 4–20 mA loop from supply to card: scale the signal, find the break with a voltmeter, and run a five-point transmitter calibration with as-found and as-left.

Comes up in

Other entries that send you here.

All of Part 5