A point reads bad or dead. At the card, read the input: current or the volts across the input resistor. If the card sees a sensible current and the screen does not, the fault is in the card or the software; swap channels to prove it. If the card sees nothing, the loop is open or unpowered: check loop power first, then half-split toward the transmitter at the junction boxes with volts across the pair: full supply before the break, nothing after (a meter in series reads 0 mA on both sides of a break). If the card sees a current that does not match the process, go to the transmitter: its own display or test terminals should agree with the card; if they do, the transmitter is misreading and needs 5.6; if they do not, the current is leaking across the terminals or to hull somewhere between, usually in a wet box.
A loop-check on a new or repaired loop is the same in reverse: simulate 4, 12 and 20 mA at the transmitter end with a loop calibrator and confirm the screen reads 0, 50 and 100 percent of range. Twenty minutes, and the point is proven from the field to the screen.
Pocket rules. Card first, then power, then half-split. Transmitter display versus card: agree means transmitter, disagree means cable. Simulate 4, 12, 20 to prove a loop. Wet boxes leak current.