4.1 · (R) Yours: something you are responsible forThe induction motor and its nameplate

Slide the drawing sideways, or open it full size.
Reading a nameplate (values from a real fire and GS pump motor)
Figure 4.1. Reading a nameplate (values from a real fire and GS pump motor)Open full size

The nameplate is the manual. Full-load amps is the number you compare the clamp meter against; running at nameplate amps is a loaded motor, well under is an unloaded one, over is trouble. Rpm tells you the poles and, against a tach, the slip (1.6). Service factor says how much over nameplate it can run continuously; 1.15 means 15 percent, 1.0 means none. Insulation class says how hot the winding may run: class F is 155°C, and a motor whose frame you cannot hold a hand on is still probably fine. IP rating says what weather it will take; a deck motor with IP55 is not sealed against a fire hose. The link arrangement on the terminal studs decides wye or delta and high or low voltage; a dual-voltage motor linked for its higher voltage on the lower supply has only a fraction of its torque (about a quarter on a US nine-lead motor, about a third on an IEC motor linked wye on its delta voltage), struggles to start and overheats under load; linked the other way, it draws far too much current and smokes.

Inside: a stator with three windings, a squirrel-cage rotor with nothing to fail but its bars and its balance, two bearings, a fan, and a terminal box. The bearings fail first, then the terminal box, then the winding, in that order on almost every ship.

When the nameplate is gone. On a real ship the plate is painted over, corroded blank, or missing, and you still need the numbers. Get them from around the motor. The starter: the overload's heater size or dial setting is the full-load amps somebody set it to, and the breaker and the cable size bracket it. The drawings: the yard's electric load analysis and the key distribution plan list every motor's kW, and the starter's own drawing usually has the amps. The sister: a second pump of the same make on the same duty has a readable plate more often than not. The machine itself: a tach uncoupled gives the poles (just under 1800 is four, just under 1200 is six); a clamp meter with the pump at its normal duty gives the real running amps, which is the number you actually care about; winding resistance compared with a known motor of the same frame gets you within a size. The frame: a tape measure and the frame tables in any motor catalog give you the frame number, and the frame number with the poles gives you the kW within one step. Write what you establish on a tag and wire it to the motor, because the next person will need it too.

Pocket rules for a blank plate. Overload setting is somebody's FLA. Yard load list has the kW. Tach for poles, clamp for real amps. Sister motor's plate. Tag what you work out.

Pocket rules. Clamp amps against the nameplate before anything else. Links match the supply voltage. A frame too hot to hold can still be normal; the clamp meter and a thermometer decide, not your hand. Write the bearing numbers down before you need them.

Electrical or mechanical. Motor, terminal box, bearings, links: electrical. The pump, fan or gear behind it: mechanical, and the electrical side is the one that says whether the motor or the load is the problem.