Two to four diesel generators feed a main switchboard, which feeds every motor, heater, lamp, and control signal on the ship. An emergency generator and a battery bank carry the services that must survive losing the main board.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Bus voltage | 440–450 V (690 V on larger plants); limits +6 / −10 % |
| Frequency | 60 Hz (50 Hz on some ships); held within ±0.5 Hz |
| Generator load at sea | 50–85 % of rated kW; PMS starts standby above 85–90 % |
| Generator minimum load on HFO | about 45–50 %; start, stop, and idle on MDO |
| Warm-up before connecting | 3–5 min; jacket water about 60 °C |
| Power factor | 0.7–0.9 lagging; alternator rated at 0.8 |
| Reverse power trip | 5–15 % of rated kW, delayed a few seconds |
| Overcurrent trip | 110–125 % delayed; instantaneous on short circuit |
| Under-frequency / under-voltage trip | 90–95 % / 60–80 % of nominal, delayed |
| Insulation resistance | 1 MΩ floor; healthy reads tens of MΩ |
| Megger test voltage | 500 V DC on 440 V gear; 1000 V on 690 V; 250 V on 220 V |
| Battery float, lead-acid / NiCd | 2.20–2.30 / 1.40–1.45 V per cell |
| Emergency generator | on the board within 45 s; 18 h fuel; a small fraction of one main set's kW |
The plant, stop by stop, as the book walks it.
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Ground lamp dark on one phase; IR alarm | Which bus — 440 or 220 V; what changed | Wet deck fitting, galley gear, floodlight | Isolate feeders in turn (Stop 6) |
| Generator trips, reverse power flag | The engine — fuel, governor | Fuel starvation, governor failure, unloaded too far | Fix the engine before re-paralleling |
| Generator trips, overcurrent delayed | kW before the trip; what started | Heavy consumer, standby not started, PMS in manual | Shed, start standby, re-parallel |
| Generator trips, overcurrent instantaneous | Which feeder breakers also tripped | Short circuit on a feeder or bus | Isolate the fault before closing anything |
| Blackout | Emergency board live? Standby started? | Last set tripped, standby not ready, bus fault | Scenario: blackout |
| Frequency low, lights dim, no trip yet | Generator kW | Overload approaching | Start standby now; shed |
| Voltage swinging, or over-voltage trip | Which set — double voltmeter | AVR, sensing fuse, replacement AVR not settled | Standby on; run that set only in parallel |
| Two sets trip within a minute, same alarm | What they share | Oil-mist detector panel, control supply, PLC | Third set on; isolate the shared device |
| Start fail; engine fired or cranked | Rpm signal; pinion action | Speed pickup, air start solenoid, starter air valve | Fix; drop set in standby order |
| Prelube low-pressure alarm after shutdown | Bearing return sight glass; pipe warm | Prelube pump air-bound | Bleed at discharge, or off 5–10 min then AUTO |
| Auto-sync won't close the breaker | Incoming Hz and voltage | Sync or governor trim fault | Bring it slightly fast by hand, back to auto |
| Preferential trip as a set is taken off | Auto or manual unload | Ramp-down fault, PF settings mismatched | Unload by hand, open breaker, stop locally |
| Motor hums, won't start | Amps on three phases | Lost phase — fuse, terminal, contact | Isolate; find the open phase |
| 24 V bus low, alarm panel dim | Charger output | Charger failed, AC fuse, bank sulfated | Restore charger; load test the bank |
Work out what you’d do, then open it.
At sea on one set. It trips, the plant goes dark, and the standby starts and closes on the dead bus. The main engine has stopped. What comes back on its own, what doesn't, and what do you do first?
Sequential restart brings back only vital machinery: engine room fans, fuel, seawater, LT and HT, main and turbo LO, stern tube LO, boiler feed. Left for you: working air compressor, air conditioning and provisions refrigeration, auxiliary boiler, galley, incinerator, some fans — keep that list posted in the ECR. Report to the bridge and the engineer in charge. Main engine: telegraph to stop, ECR control, confirm LO, HT, and cylinder lube, reset shutdowns, restart at dead slow, hand back. Bring a second set online and check the one that recovered the bus before heavy loads go back. Forget the air compressor and control air and start air bleed down within the hour — the engine you just restarted needs both.
Blackout; neither standby set starts. The emergency generator is carrying the emergency board. How do you get a main set on?
Only sets whose control panels and prelube pumps are fed from the emergency board can start — know which on your ship. Emergency air receiver up, with the emergency compressor if needed. Start the MDO flushing pump to feed that set by head. Local, prelube confirmed, start, and close on the dead main bus at nominal voltage and frequency; it carries limited load until the main fuel pumps run. Watch the emergency generator's kW throughout. If the interconnector must back-feed the main board, shed every non-vital load first.
Two sets on the bus. An oil-mist alarm trips one; a minute later the second trips on the same alarm. A standby starts and just catches the bus. What failed, and what now?
Two crankcases failing within a minute is unlikely; one detector panel serving both is likely. Get a third set ready, then check the tripped engines locally — crankcase doors, smell, LO pressure — before restarting one. Isolate the faulty detector head per the maker and clean or replace it; until then, keep a set in reserve. When a fault spreads to a second identical machine, look first at what they share.
Morning watch after a night of rain. The 440 V ground lamps show one phase dark; the monitor reads 15 kΩ. Where do you start?
Rain says deck. Open the deck lighting feeder; if the lamps even up, it is a floodlight with water in it, found breaker by breaker at its panel. If not: deck receptacles, windlass and winch starters, deck crane; then galley, laundry, heaters. A partial recovery means more than one ground. The lamps say which phase; the megger on the isolated circuit says which cable.