Contactor. As 4.6, with one extra: compressor motors have high inrush and some have part-winding or wye-delta starts, so the contactor arrangement may be two or three contactors and the drawing must be followed.
Pressure switch. Isolate the refrigerant side at the switch's valve if it has one, or recover if it does not; this is the moment the EPA card matters. Match the range. Set cut-out to the plant's figure and the differential, where it has one, so it does not chatter (most manual-reset high-pressure switches have a fixed differential), and check against the gauge as the plant runs.
Fan motor. Condenser and evaporator fans are small single- or three-phase motors, often with a run capacitor (0.13 for testing it). Match the frame, the speed and the rotation; a condenser fan that blows the wrong way runs the plant hot and trips it on high pressure.
Controller rewire. Photograph before. Sensor inputs are polarized or typed (a thermistor on a thermocouple input reads the panel's own temperature, a believable wrong number); outputs drive solenoids, heaters and fans through relays or directly. Land them by the photo and the manual, power up, and watch the controller's display agree with reality before you close the door.
Pocket rules. Compressor starts are often two contactors. Pressure switch: isolate or recover, then set. Fan rotation by airflow. Controller: photo, type the sensors, confirm the display.