The refrigeration plant's electrical side is a motor and a chain of safeties. The compressor runs when its contactor pulls in, and the contactor's coil is in series with the high-pressure switch, the low-pressure switch, the oil pressure switch with its time delay, the motor's own protection, and the controller's demand. Any one of them open and the compressor stops, and the lamp or the controller's display tells you which, if you look before you reset. Around it: fan motors on the condenser and evaporators, solenoid valves on the liquid lines to each room, defrost heaters on a timer or a controller, and the room thermostats.
The electrical and the refrigeration faults talk to each other: a high-pressure trip on a water-cooled plant is usually lost cooling water (pump, strainer, valves), fouled tubes or air in the system, and on an air-cooled unit a condenser fan or dirty condenser; a low-pressure trip is low charge or a solenoid that did not open, though on a pump-down plant the low-pressure switch stops the compressor every normal cycle, so the fault is short-cycling or warm rooms, not the stop itself; an oil pressure trip after a long run is oil, not electrics. The ETO's job is to say which it is, and your refrigerant certificate (the EPA 608 card on a US-flag ship, F-gas or the flag's own elsewhere) is the reason you are allowed to open the refrigerant side when it is both.
Pocket rules. Which safety opened, before you reset. HP: cooling water, or the fan on an air-cooled unit. LP: charge or solenoid. Oil: oil. Defrost heaters and their timer are the usual cause of an iced-up evaporator.
Yours or not. Motors, contactors, switches, solenoid coils, heaters, controllers, timers: yours. Refrigerant side: yours if you hold the card, otherwise the engineers or a technician.