7.6 · (F) A job you do with your handsIsolate a loop fault, swap a detector or call point

Slide the drawing sideways, or open it full size.
A loop fault on a real-style addressable loop
Figure 7.6. A loop fault on a real-style addressable loopOpen full size

Loop fault. The panel says which addresses are missing. The devices on either side of the missing range are the isolators that have done their job. Open the loop at each of them and meter the dead section: a short between the loop conductors, a short to hull, or an open. Half-split along the section at the device bases until you have it between two bases; the cable between them is the fault, and it is usually a drill, a gland or water. Repair, close the loop, reset the panel and confirm every address is back.

Device swap. Detectors twist off their bases; call points unclip or unscrew. The new device needs the same address as the old one, set by switches or by the panel's programming tool, or the panel will report a device it does not know. Fit, program if needed, test it (test smoke, test heat, or the call point's key) and confirm the panel shows the right text for it. Disable the zone while you work and enable it afterward, and log both.

Pocket rules. Lost addresses bracket the fault. Open at the isolators and meter the section. Same address on the new device. Disable, work, test, enable, log.

Work it

Built for this entry. Lessons first, then the simulator for free play.

All of Part 7