0.13The multimeter: every position on the dial

Slide the drawing sideways, or open it full size.
The multimeter dial
Figure 0.13. The multimeter dialOpen full size

Most people use two positions on the meter and never find out what the rest are for. Here is the whole dial, each one with the job it does on a ship.

V AC and V DC. The usual. One habit: always test the meter on a known live source before and after you prove something dead. A meter with a broken lead, a lead left in the amps receptacle or a flat battery reads zero on a live bus.

LoZ (low impedance). A normal meter has such high input resistance that a long cable or a dirty contact can show phantom volts, 80 V on a wire that is actually dead. LoZ loads the circuit slightly and makes the phantom disappear. Use it whenever a reading makes no sense, and whenever you are proving dead.

mV. Across a shunt to read current, or across a closed contact under load to see the voltage drop that says the contact is going bad.

Ω (resistance). Dead circuits only. Coil resistance against the nameplate, heater elements, the three windings of a motor against each other (they should match within a few percent; one high is a bad connection, one low is a shorted turn), and the fuse-rating arithmetic from 1.1.

Continuity (the beeper). Fuses, wires end to end, contacts open and closed. Fast, but it only says under a few ohms; it does not say good insulation and it does not say zero.

Diode. The rotating rectifier on the alternator; the diodes in a charger or power supply; the LED in a pilot light. Reads the forward voltage drop one way, open the other.

Capacitance. You will use it more as more ships carry drives, soft starters and single-phase motors. Isolate the circuit, discharge the capacitor through a resistor (never a screwdriver), disconnect at least one lead so you are not reading the circuit around it, and measure. Compare with the printed value: within 10 to 20 percent is a live capacitor; well under is a dying one; zero is open; a reading that will not settle usually means it is leaking. Motor-start and run capacitors on single-phase fans and pumps, the capacitors in a soft starter's bypass, the DC bus bank on a drive, the filter capacitors in a power supply that reboots itself: all of them die quietly and this is how you catch it.

Hz. Confirms the frequency on a bus or at a drive output when the panel meter is suspect.

mA and µA. In series in a 4–20 mA loop; across a loop's test terminals. The one range where the meter's own fuse goes if you touch volts by mistake. The volts ranges are not fused and keep working; the current range reads zero until the fuse is changed.

Temperature. With the thermocouple probe: a bearing, a lug, a transformer, a motor frame. A cheap thermal camera has replaced this for most jobs, but the probe still goes where the camera cannot see.

Min/Max and peak hold. Start a motor and read its inrush; watch a voltage that dips when something else starts; catch an intermittent that only shows for a moment. Set it and walk away.

Pocket rules. Prove the meter on a known source first. LoZ when the reading is strange. mA range: check the fuse before you trust a zero. Capacitors: isolate, discharge, disconnect, then measure. CAT III 600 V is the minimum for anything on the switchboard; CAT IV for the generator terminals.