Calibrate. Isolate the process and vent. Connect a test source (a hand pump for pressure, a reference bath or a decade box for temperature) and a reference gauge or calibrator. Check zero with no input: the output should be 4.0 mA. Check span at full range: 20.0 mA. Check the middle. Adjust zero and span, on the unit's buttons, by HART, or on the old ones with screwdriver pots, and re-check both, because adjusting one moves the other. Record as-found and as-left.
Replace. Match the range (a 0–10 bar unit where 0–25 bar belonged reads full scale at 10 bar and tells you nothing above it), the process connection, the electrical connection and the output type. Set the new unit's range to match the old one and the card's scaling before you trust the screen; a new unit arriving with a different range reads correctly in mA and wrong in bar. Loop-check it from the field to the screen when you are done (5.3).
Pocket rules. Zero, span, middle, repeat. Record as-found. Match the range, then the connections. Loop-check to the screen.