5.5 · (R) Yours: something you are responsible forPressure, level and flow transmitters and switches

Slide the drawing sideways, or open it full size.
Pressure, level and flow sensing points
Figure 5.5. Pressure, level and flow sensing pointsOpen full size

A transmitter gives a number; a switch gives yes or no. Pressure transmitters sit on isolation valves so they can be removed; a transmitter that reads zero may be on a valve someone shut. Level is measured by differential pressure, by a float, by radar or ultrasonic from the tank top, or by a capacitance probe, and each one lies in its own way: DP cells read wrong when a leg fills or drains, radar sees foam, floats stick, probes coat. Flow switches are paddles or thermal units that fail stuck and alarm when there is flow. Pressure switches have a setpoint and a differential, and a switch that chatters has its differential set too tight.

The thing to carry: every reading has a physical path from the process to the sensing element, and that path fails as often as the electronics. An isolation valve, a blocked impulse line, a frozen tube, a float wedged in a well. Look at the path before you look at the loop.

Pocket rules. Transmitter zero: is the valve open? Level lies according to its type. Switch chatter: differential. Check the process path before the loop.