A transmitter gives a number; a switch gives yes or no. Pressure transmitters sit on isolation valves so they can be removed; a transmitter that reads zero may be on a valve someone shut. Level is measured by differential pressure, by a float, by radar or ultrasonic from the tank top, or by a capacitance probe, and each one lies in its own way: DP cells read wrong when a leg fills or drains, radar sees foam, floats stick, probes coat. Flow switches are paddles or thermal units that fail stuck and alarm when there is flow. Pressure switches have a setpoint and a differential, and a switch that chatters has its differential set too tight.
The thing to carry: every reading has a physical path from the process to the sensing element, and that path fails as often as the electronics. An isolation valve, a blocked impulse line, a frozen tube, a float wedged in a well. Look at the path before you look at the loop.
Pocket rules. Transmitter zero: is the valve open? Level lies according to its type. Switch chatter: differential. Check the process path before the loop.