Two families and they fail differently. An RTD is a resistor whose value changes with temperature, 100 ohms at 0°C for a Pt100, about 138 ohms at 100°C; it is accurate and slow, and it is what you find on bearings, windings, cooling water and lube oil. The third wire cancels the resistance of the cable so a long run does not read as extra degrees; a three-wire RTD connected as two-wire reads high. Ohm it against the table and it either agrees or it does not. A thermocouple is two dissimilar wires joined at the hot end, making a small voltage that depends on the difference between that junction and the cold end at the input; it is fast and rugged, and it is what you find on exhaust gases. The input compensates for its own temperature, and the extension wire from the thermocouple to the input must be the same type, because a splice in copper is a second thermocouple that reads wrong. A thermocouple with a broken junction reads open; one with a corroded junction reads low and slow.
Pocket rules. RTD: ohm it against the table. Three wires, connected as three. Thermocouple: matching extension wire, correct polarity, no copper splices. Exhaust reading low and slow is a corroded junction.