A reading looks wrong. Raw value against the screen. A neighboring sensor on the same system. The process path (5.5). Then the loop (5.3). Then the card. The screen last.
An alarm that will not clear. The limit against the raw value. A point that is genuinely out of range is the plant, not the system.
A nuisance alarm that comes and goes. A loose connection in the loop, a wet box, a sensor on the edge of its limit. Trend it.
Frozen screen or operator station. Power, then the network, then the station itself. The plant is still being watched by the process stations; the screen is a window, not the watcher.
Lost communication to a cabinet. 5.14, starting with the switch or the serial chain nearest the dead cabinet.
A PLC output that will not come on. 5.8: find the input it is waiting for.
A spurious shutdown. 5.12: the display says which input.
Everything in one cabinet dead. Its power supply, its fuse, its feeder. Then the UPS that feeds it (7.1).