The cabinets talk to each other and to the screens over networks, and the networks fail in their own ways. Serial links, RS-485 mostly, are a two-wire chain from device to device with a termination resistor at each end; they fail when the chain is broken, when a resistor is missing or doubled, when two devices have the same address, or when the polarity of the pair is swapped at one device. Modbus is the language most of them speak over the wire; a device that is powered and wired and still silent usually has the wrong address or baud rate. Ethernet links cabinets and operator stations through switches; they fail when a switch loses power, a cable is unplugged, or a duplicate IP address appears, usually from a laptop. Fiber carries the long runs between the engine room and the bridge; it fails when a connector is dirty or a bend radius is broken, and it is tested with a light source and a meter, not a multimeter.
Pocket rules. Serial: termination, address, polarity. Modbus silent: address or baud. Ethernet dead: switch power, then the cable, then a duplicate IP. Fiber: clean the connectors first. Keep laptops off the automation network unless you mean it.