5.13 · (R) Yours: something you are responsible forPackaged controllers: boiler, purifier, compressor, HVAC

Slide the drawing sideways, or open it full size.
Packaged controllers are all the same cabinet
Figure 5.13. Packaged controllers are all the same cabinetOpen full size

Every major auxiliary comes with its own control cabinet from its maker, and they are all the same thing inside: a power supply, a controller, inputs from the machine's own sensors, outputs to its own solenoids and motors, a screen on the door, and a common alarm contact to the ship's system. The boiler cabinet runs the burner sequence, the flame safeguard and the water level; the purifier cabinet runs the bowl's discharge timing and watches the water transducer; the compressor cabinet does loading and unloading and the temperature trips; the HVAC cabinet does compressor staging, defrost and the pressure switches.

What is yours inside them: the power supply, the I/O wiring, the sensors and solenoids on the machine, the common alarm to the ship, and the screen. What is the engineers': the machine. What is the maker's: the program and the setpoints that protect the machine, which the manual lists and which are not changed to stop an alarm. The screen's alarm history is the first thing to read, and the maker's manual is the second, because these cabinets have fault codes that mean something specific.

Pocket rules. Same cabinet inside, every time. Alarm history first, manual second. Sensors and solenoids are yours; setpoints are the maker's. The common alarm wire to the ship is the one that gets forgotten.

Yours or not. As above. The flame safeguard on a boiler is the one controller where you call the vendor before you do anything you are not certain of.

Work it

Built for this entry. Lessons first, then the simulator for free play.

Comes up in

Other entries that send you here.

All of Part 5