An engine turns a brushless alternator, and two separate controllers decide what comes out. The governor sets speed, so frequency and kW. The AVR sets excitation, so voltage and kVAR. Hold those two loops apart in your head and most generator troubleshooting sorts itself.
The alternator is three machines on one shaft plus a box. The main machine is a spinning DC field inside a fixed three-phase winding; the 450 V comes out of the fixed winding. The exciter is a small generator turned inside out, its field on the frame fed DC by the AVR, its three-phase output on the shaft. Six diodes on a plate on the shaft turn that output into DC for the main field, which is how there are no brushes. The AVR reads the output voltage through sensing leads and pushes current into the exciter field until the voltage is right. Many machines add a small permanent-magnet generator on the shaft end to power the AVR, so the set can build voltage with nothing else alive and hold short-circuit current long enough to trip a breaker.
On the drawing, follow the right-hand loop: load rises, volts sag, the AVR sees it, more exciter current, volts recover. Then the left-hand loop: load rises, speed sags, the governor sees it, more fuel, speed recovers. Two loops, two knobs, two separate sets of symptoms. The frequency meter tells you which loop is sick: steady frequency with swinging volts is the AVR side; swinging frequency is the engine side.
Also in the enclosure and also yours: the stator and bearing RTDs, the air filters, and the space heater that should be the one thing energized when the set is stopped.
Reading the real sheet. The maker's AVR connection diagram looks busy and is the same loop drawn with every part named. The AVR (A1) takes its working power from a small control transformer (T9) off the generator terminals, senses the output voltage on the same terminals, reads the droop CT (T4) in one phase, and fires a thyristor (V28) that feeds DC through the exciter field terminals F1 and F2. The exciter's armature, on the shaft, feeds the rotating rectifier (V2) with its protective varistor, and that DC goes into the main field. Three more things worth finding on your own ship's sheet: the reference setter (VR), which is the voltage adjust on the panel; the 187X de-excitation contact, which lets the differential relay short the exciter field when it sees a winding fault, so the voltage dies away as fast as a brushless machine allows, a second or so, while the breaker trips; and the field-flashing provision, usually a note saying no more than 24 V DC and only if needed.
Pocket rules. Frequency steady, volts wrong: AVR, diodes, sensing. Frequency wrong: governor, fuel, engine. Never megger through the AVR. Find the diode plate on day one.
Electrical or mechanical. Alternator, AVR, exciter, diodes, PMG, RTDs, heater, sensing and droop CTs, speed pickup, actuator wiring and the electronic governor box: electrical. Engine, fuel rack, mechanical governor internals: mechanical. Rewind, bearing on a big machine, dropped diode plate: vendor, decided with the engineer in charge.