1.16Stored energy and arc flash

The four places it hides, and when to worry

Slide the drawing sideways, or open it full size.
Four places stored energy hides
Figure 1.16. Four places stored energy hidesOpen full size

Where you'll meet it. Four times, specifically. One: you open a switchboard cubicle to work on a breaker and the breaker is open, so it is safe, except the closing spring is charged and the breaker will close the instant a close command arrives or a finger finds the wrong latch. Discharge the spring and read the indicator before you reach in. Two: you isolate a drive and open the cover; the bus capacitors hold about 620 V for minutes, and the lamp that says so is sometimes burned out. Wait, then meter the bus. Three: you open a feeder to a big pump and the pump keeps spinning for a minute on its own inertia, or because a check valve is passing and the flow is driving it; a spinning motor is a generator and its terminals are live. Prove dead at the motor, not at the breaker. Four: batteries have no off switch. Pull the fuse, cover the terminals, keep the wrench away from the bank.

The idea. 450 V is not low voltage in the sense that matters. A bolted fault on a main switchboard can release enough energy in a cycle to burn through clothing from a meter away, fed by generators that take time to trip. Before you open a cubicle, know where the bus is, whether the springs are charged, and whether there is a capacitor bank in the box. Lock out what can be locked out. The arc-flash label on the board tells you the boundary and the gear; if there is no label, treat it as the worst case the board can make.

Used in: 3.1, 3.1b, 3.8, 4.8.

Work it

Built for this entry. Lessons first, then the simulator for free play.

All of Part 1