Most of this is simple and the mistakes are in the matching, not the work.
Breakers. Match frame size, trip rating, interrupting rating and poles. A breaker with a lower interrupting rating than the board's fault level is a bomb that works fine until the day of the fault. Lock out the feeder above, prove dead on both sides of the breaker you are changing (its line side is the load side of the feeder you locked out), note where every wire goes, and torque the lugs to the label.
Fuses. Same type, same rating, same speed. A fast fuse where a time-delay belongs will blow on every motor start; a time-delay where a fast one belongs will let a sensitive load cook. Find out why it blew before you fit the new one; a fuse is a symptom.
Relays. Match coil voltage and contact arrangement. Photograph the base before you pull it; relays in the same panel are often different inside identical housings.
Terminals. Any terminal that has been hot, discolored or loose is replaced, not retightened; the spring is gone. Strip to the right length, ferrule stranded conductors where the terminal expects it, and pull-test every one.
Pocket rules. Interrupting rating is not optional. A fuse is a symptom. Photograph before you pull. A hot terminal is a dead terminal.