3.7c · (F) A job you do with your handsGround, short, open: which do you have?

Slide the drawing sideways, or open it full size.
Three faults, three tests
Figure 3.7c. Three faults, three testsOpen full size

Three different faults, three different tests, and they get mixed up because people start with the meter instead of the symptom.

The symptom tells you which to test for. A breaker that trips the instant it closes, or a fuse that blows on energizing, is a short: conductor to conductor, or conductor to hull on a grounded system. Lamps uneven or an insulation alarm with everything still running is a ground on an ungrounded system. A load that is simply dead with its breaker closed and its fuses good is an open.

The tests, with the circuit isolated and locked out. For a short: ohms between each pair of conductors; with the motor connected a healthy circuit reads the winding resistance, equal between all three pairs, a few ohms on a small motor and a fraction of an ohm on a big one; a short reads near zero, and the pair that reads low is the pair. On a big motor the windings read so low that you disconnect at the terminal box and test the cable and the motor separately. For a ground on a motor or a power cable: megger each conductor to hull; healthy reads megohms, grounded reads kilohms or less. An ohmmeter is not enough there, because a wet winding can read open on an ohmmeter and fail at 500 V. On a lighting circuit the multimeter on ohms to hull is the test: there is a ground or there isn't. For an open: continuity end to end on each conductor, which means someone at the far end or a jumper between conductors at the far end so you can read a loop from one place.

The ones that fool you. A ground in a motor winding, wye or delta, reads as a ground on all three conductors, because they are connected inside; that is normal, and the cable is not grounded three times. A shorted turn inside a winding reads as one winding a little lower than the other two, not as zero. An open that is intermittent, a cracked conductor in a flexing cable, reads fine on the bench and open on the ship; wiggle the cable while you watch the meter.

Pocket rules. Trips instantly: short, ohm between conductors. Lamps uneven: ground, megger to hull on a motor or cable, ohms to hull on lighting. Dead load: open, continuity end to end. Ohmmeter for shorts and opens, megger for grounds on motors and cables. Wiggle the cable.

Work it