What the frequency meter is really telling you
Where you'll meet it. Day one, you look at the generator panel: 450 V, 59.3 Hz. Is 59.3 an electrical problem? No. Frequency is the engine's speed and nothing else; the meter is a tachometer with a different scale. A set at 59.3 is a governor set low or an engine losing the fight with its load, and it is the engineers' knob, though you will be the one who reads the meter first and knows which way to point.
The idea. The meter reads RMS, the effective value; the peak is 1.4 times that, about 640 V on a 450 V system. Nothing rated under 600 V belongs on the switchboard; 600 V is an RMS rating, the first standard one above 450 with margin, and its tests allow for the peaks and spikes. Sixty hertz is sixty cycles a second, set by the engine turning the alternator. Phase is the timing difference between two waves, and three-phase is three waves 120 degrees apart; everything with a rotating field is built on that spacing.