The pump that started by itself
Where you'll meet it. A cargo hold bilge pump starts with the well dry and runs until somebody notices. The control circuit is a float switch in series with the coil, so the coil should be dead with the float down. Open the box and there is a jumper across the float switch terminals, left from a test last hitch. A jumper is a parallel path, and a parallel path means the coil has a second way to get power. The reverse problem is the common one: a circuit that will not work has one open somewhere in a series string, and every contact in the string is a suspect.
The idea. Everything that must be true is wired in series: fuse, stop, overload, interlock, coil. One open anywhere, the string is dead. Anything that can happen for more than one reason is wired in parallel: two start buttons, a hold-in contact around a momentary one. Won't run: look for the open in the series string. Runs when it shouldn't: look for the parallel path, a welded contact, a jumper.