1.14What a VFD does to a sine wave

The ground that only shows when the thruster runs

Slide the drawing sideways, or open it full size.
Inside a VFD, and the leakage it makes
Figure 1.14. Inside a VFD, and the leakage it makesOpen full size

Where you'll meet it. The insulation monitor alarms every time the bow thruster runs and clears when it stops. The hunt finds nothing wet. What it is finding is the drive: the inverter's fast switching pushes current through the capacitance of a long motor cable to the hull, and the monitor, which is looking for leakage, sees leakage. It is not a ground you can fix with a gasket; it is the drive doing what drives do, and the answer is the drive's own filter and the monitor's setting, not another afternoon in the thruster room. Knowing that saves the afternoon. The other thing the drawing shows is the DC bus, around 620 V and lethal for minutes after power is off. Wait for the lamp, then prove it with the meter.

The idea. A variable frequency drive rectifies the 440 V to a DC bus, then switches that DC on and off thousands of times a second to make a pulse train whose average is a sine wave at whatever frequency the drive is told. Motor speed follows frequency. Three consequences: a lethal DC bus after power off; harmonics and capacitive leakage back onto the ship; and a fault log that usually knows more about what happened than you do, so read it first.

Used in: 3.6, 4.8, 4.9.

Work it

Built for this entry. Lessons first, then the simulator for free play.

Comes up in

Other entries that send you here.

All of Part 1